Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 Appendix 4 Braking resistance
178
Appendix 4 Braking resistance
1.1 Braking resistance
The motor’s electric potential energy will charge inverter’s capacitance up
reversely if speed of the motor decends too quickly or load of the motor wobbles
too quickly while the inverter is running, which will increase the voltage upon
power modules suddenly and is easy to make the inverter damaged. The inverter
will control it according to load size and performance. You only need to connect
external braking resistance to realize timely energy discharge when the braking
function is needed. To connect external resistance is a kind of energy consumption
braking mode, as all the energy is consumed by the braking resistance.
We can add built-in braking unit for EDS1000-2S0004~2S0037 with additional
cost upon receival of your requirement; EDS1000-4T0007G~4T0150G have
built-in braking unit, but no braking resistance.
When braking function needed, please connect external braking resistance
according to below table.
Braking unit&braking resistance configuration and External braking
resistance configuration table
Type
Built-in braking
unit
Built-in braking
resistance
External
braking
resistance
Qty.
Power of
external
braking
resistance
EDS1000-2S0004
Need to be
customized
N/A ≥150Ω 1 200W
EDS1000-2S0007
Need to be
customized
N/A ≥100Ω 1 250W
EDS1000-2S0015
Need to be
customized
N/A ≥70Ω 1 400W
EDS1000-2S0022
Need to be
customized
N/A ≥50Ω 1 600W
EDS1000-2S0037
Need to be
customized
N/A ≥30Ω 1 1000W
EDS1000-4T0007G Yes N/A ≥300Ω 1 200W
EDS1000-4T0015G Yes N/A ≥300Ω 1 200W
EDS1000-4T0022G Yes N/A ≥300Ω 1 200W
EDS1000-4T0037G Yes N/A ≥125Ω 1 400W
EDS1000-4T0055G Yes N/A ≥80Ω 1 650W
EDS1000-4T0075G Yes N/A ≥80Ω 1 650W
EDS1000-4T0110G Yes N/A ≥50Ω 1 1000W
EDS1000-4T0150G Yes N/A ≥40Ω 1 1000W