Service manual

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 Appendix 2 The manual of EDS1300 middle frequency inverter
167
Fd.06 Set freq. of previous failure Set freq. of previous failure 0.01Hz 0 *
Fd.07 output freq. of previous failure output freq. of previous failure 0.01Hz 0 *
Fd.08 output current of previous failure output current of previous failure 0.1A 0 *
Fd.09 output voltage of previous failure output voltage of previous failure 1V 0 *
Fd.10
DC bus-bar voltage of previous
failure
DC bus-bar voltage of previous failure 1V 0 *
Fd.11
Load motor speed of previous
failure
Load motor speed of previous failure 1(r/m) 0 *
Fd.12
Module temperature of previous
failure
Module temperature of previous failure 1 0 *
Fd.13
Input terminal status of previous
failure
Input terminal status of previous failure 11111111 *
Fd.14
Accumulative run time of
previous failure
Accumulative run time of previous
failure
0 *
FFPassword and manufacturer function parameter group
Function
code
Name Setting range
Min.
unit
factory
default
Modific
-ation
FF.00 User password 00009999 1 0000 ×
FF.01 Manufacturer password 00009999 1 0000 ×
FF.02-
FF.0X
Manufacturers special parameter
CSupervision function parameter group
Function
code
Name Description
Min.
unit
Factory
default
Modific
-ation
C-00 Set frequency Current set frequency 0.01HZ
C-01 Output freq. Current output freq. 0.01HZ *
C-02 Output current Virtual value of current output current 0.1A *
C-03 Output voltage Virtual value of current output voltage 1V *
C-04 DC bus-bar voltage Current DC bus-bar voltage 1V *
C-05 Load motor speed
Product of output frequency and load
motor speed emendation factor
1(r/m) *
C-06 Module temperature IGBT heat sink temperature 1 *
C-07 Run time Inverter electrification run time 1h *
C-08 Accumulative run time Inverter accumulative run time 1h *
C-09 Input terminal status Switch value input terminal status ―― *
C-10 Output terminal status Switch value output terminal status ―― *
C-11 Analog input VCI Analog input value of VCI V *
C-12 Analog input YCI Analog input value of YCI V *
C-13 Analog input CCI Analog input value of CCI V *
C-14 Exterior pulse input Exterior pulse input 0.1KHz *