www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 Appendix 2 The manual of EDS1300 middle frequency inverter
163
F5.03
Input terminal X4
function selection
Same as above ×
F5.04
Input terminal X5
function selection
Same as above ×
F5.05
Input terminal X6
function selection
Same as above ×
F5.06
Input terminal X7
function selection
Same as above ×
F5.07
Input terminal X8
function selection
Same as above ×
F5.08
FWD/REV run mode
selection
0: double-line control mode 1
1: double-line control mode 2
2: three-line control mode 1
3: three-line control mode 2
1 0 ×
F5.09
UP/DOWN
velocity
0.01-99.99Hz/s 0.01Hz/s 1.00Hz/s ○
F5.10
Open circuit
collector
output terminal
OC1 output setting
0: inverter running(RUN)
1: frequency arriving signal(FAR)
2: frequency level detect signal (FDT1)
3: reserved
4: overload warning alarm signal (OL)
5: output frequency reach high limit(FHL)
6: output frequency reach low limit(FLL)
7: inverter under voltage blockage stop (LU)
8: external failure stop-runnin(EXT)
9: inverter zero rotate speed running
10: PLC running
11: simple PLC section running finished
12: PLC finish a cycle running
13: reserved
14: inverter ready to run (RDY)
15: inverter failure
16: swing frequency high and low limit restriction
17: interior counter reach final value
18: interior counter reach specified value
19: set run time arriving
20: interior timing arriving
21: OC1-variable frequency for the 1
st
pump
OC2-power source for the 1
st
pump
OC3- variable frequency for the 2
nd
pump
OC4-power source for the 2
nd
pump
22: reserved
23: reserved
24: reserved
1 0 ×
F5.11
Open circuit
collector output
terminal OC2
output setting
Same as above 1 0 ×
F5.12
Open circuit
collector output
terminal OC3
output setting
Same as above 1 0 ×
F5.13
Open circuit
collector output
terminal OC4
output setting
Same as above 1 0 ×