F3.08 proportion gain Kp 0.000-9.999 0.001 0.050 ○
F3.09 Integral gain Ki 0.000-9.999 0.001 0.050 ○
F3.10 Differential gain Kd 0.000-9.999 0.001 0.000 ○
F3.11 Sampling cycle T 0.01-1.00s 0.01s 0.10s ○
F3.12 Deviation margin 0.0-20.0(%)percentage relative to 10.00V 0.1(%) 2.0(%) ○
F3.13
Integral separation
PID adjusting
threshold
0.0-100.0% 0.1% 100.0% ○
F3.14
Closed-lop preset
frequency
0-upper limit frequency 0.01Hz 000.0hz ○
F3.15
Closed-loop preset
frequency holding
time
0.0-6000s 0.1s 000.0s ○
F3.16 reserved
F3.17 reserved
F3.18 reserved
F3.19 reserved
F3.20 reserved
F3.21 reserved
F3.22 reserved
F3.23 reserved
F3.24 reserved
F3.25 reserved
F3.26 reserved
F3.27
Closed-loop adjusting
characteristic
0: Forward function
1: Reverse function
0 ○
F3.28
LED initial
supervision parameter
selection
0: set frequency
1: output frequency
2: output current
3: output voltage
4: DC bus bar voltage
5: motor speed
6: heat sink temperature
7: run time
8: accumulative run time
9: input terminal status
10: output terminal status
11: analog input VCI/PID provision
12: analog input CCI/PID feedback
13: analog input YCI
14: exterior pulse inputs
1 ○
F3.29 YCI run-in delay time 0.0-999.9s 0.1 10.0 ○
F3.30
Failure relay TA,TB,
TC function selection
0: inverter running(RUN)
1: frequency arriving signal(FAR)
2: frequency level detect signal (FDT1)
3: reserved
4: overload warning alarm signal (OL)
5: output frequency reach high limit(FHL)
6: output frequency reach low limit(FLL)
7: inverter under voltage blockage stop (LU)
8: external failure stop-running(EXT)
9: inverter zero speed running
10: PLC running
11: simple PLC section running finished
12: PLC finish a cycle running
13: reserved
15 ○