F2.45 Jumping freq. 1 0.00400.00Hz 0.1Hz 0.00Hz ×
F2.46 Jumping freq. 1 range 0.0030.00Hz 0.1Hz 0.00Hz ×
F2.47 Jumping freq. 2 0.00400.00Hz 0.1Hz 0.00Hz ×
F2.48 Jumping freq. 2 range 0.0030.00Hz 0.1Hz 0.00Hz ×
F2.49 Jumping freq. 3 0.00400.00Hz 0.1Hz 0.00Hz ×
F2.50 Jumping freq. 3 range 0.0030.00Hz 0.1Hz 0.00Hz ×
F2.51 Setting run time 065535 hours 1 0
F2.52 Accumulative run time 065535 hours 1 0 *
F2.53
RS485/232 communication
frame format selection
0: a ASCII frame of 14 byte or
18 byte
1: a hex frame of 8 byte or 10
b
yte, original response not
changed
2: a hex frame of 8 byte or 10
b
yte, 12 command has no
response
3: a hex frame of 8 byte or 10
b
yte, 14 command has no
response
4: a hex frame of 8 byte or 10
byte, both 12 and 14
command have no response
1 0 ×
F3Closed-loop run function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F3.00
Closed-loop run
control selection
0: closed-loop control ineffective
1: PID closed-loop control effective
2: reserved
1 0 ×
F3.01
Provision channel
selection
0: digital provision
1: VCI analog 010V voltage provision
2: CCI analog provision
3: keypad potentiometer provision
1 1
F3.02
Feedback channel
selection
0: VCI analog input voltage 010V
1: CCI analog input
2: VCI+CCI
3: VCI-CCI
4: Min { VCI, CCI }
5: Max { VCI, CCI }
6: pulse feedback
1 1
F3.03
Specified value digital
setting
0.00~10.00V(setF3.00=1,F3.21=9.999) 0.01 0.00
F3.04
Minimum specified
value
0.0maximum specified value; percentage
relative to 10.00V
0.1(%) (0.0)%
F3.05
feedback value
responding to
minimum specified
value
0.0100.0(%) 0.1(%) (0.0)%
F3.06
maximum specified
value
Minimum specified value
100.0(%)
0.1(%) 100.0(%)
F3.07
feedback value
responding to
maximum specified
value
0.0100.0(%) 0.1(%) 100.0(%)