Service manual

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 Appendix 2 The manual of EDS1300 middle frequency inverter
155
run mode 1: stop
F0.13
Torque boost
mode
0: manual boost
1: automatic boost
1 0
F0.14 Torque boost 0.012.0 (%) 0.1(%) 00.5(%)
F0.15 V/F curve setting
0: constant torque curve
1: degressive torque curve 1(the 2.0nd
power)
2: degressive torque curve 2 (the 1.7th
power)
3: degressive torque curve 3 (the 1.2th
power)
4: End-user sets VF curve himself(determined
by F2.37~F2.44)
F2.37 VF Freq. value 0
F2.38 VF voltage value 0
F2.39 VF Freq. value 1
F2.40 VF voltage value 1
F2.41 VF Freq. value 2
F2.42 VF voltage value 2
F2.43 VF Freq. value 3
F2.44 VF voltage value 3
Remark: VF frequency and voltage can’t be 0
or maximum
1 0 ×
F0.16 G/P type setting
0: G type
1: P type
1 0 ×
F1Start, stop, brake function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F1.00 Start-up run mode
0: start at start-up freq.
1: first brake, then start at start-up freq.
2: reserved
1 0 ×
F1.01 start-up freq. 0.0100.0Hz 0.1Hz 0.0Hz
F1.02 start-up freq. duration 0.020.0S 0.1s 0.0s
F1.03
DC brake volt. at
start-up
015(%) 1 0
F1.04
DC brake time at
start-up
0.020.0S 0.1s 0.0s
F1.05 Stop mode
0: Dec stop
1: free stop
2: DecDC brake stop
1 0 ×
F1.06
DC brake initiative freq.
when stop running
0.015.00Hz 0.1Hz 0.0Hz
F1.07
DC brake time when
stop running
0.020.0s 0.1s 0.0s
F1.08
DC brake voltage when
stop running
015(%) 1 0