Service manual

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 2 Type and specification of the inverter
9
Frequency 0Hz-400Hz
Over loading capacity
G type: 150% of rating current for1 minute200%
of rating current for 0.5 second
P type: 120% of rating current for 1 minute
Control
performance
Control mode
Speed sensorless slip vector control,
open loop V/F control
Speed regulation range 1: 100
Start-up torque 150% of rating torque at 1 Hz frequency
Running speed stable state
precision
≤±0.5% of rating synchronous speed
Frequency precision
Digital setting: max. frequency×±0.01%analog
setting: max.frequency×±0.5%
Frequency
resolution
Analog setting 0.1% of max. frequency
Digital setting precision : <100Hz 0.01Hz; 100Hz: 0.1Hz
Exterior impulse 0.5% of max. frequency
Torque boost
Automatic torque boost, manual torque boost
0.1%~12.0%
V/F curve (volt. frequency
characteristic)
Set rating frequency randomly at range of
5~400Hzcan choose constant torque, degressive
torque 1, degressive torque 2, degressive torque 3
and user-defined V/F in total 5 kinds of curve
Accelerating decelerating curve
2 modes: straight line accelerating decelerating and
S curve accelerating decelerating; 7 kinds of
accelerating decelerating time (unit minute/second
can be optioned), max. time 6000 minutes.
brake
Power consumption
brake
Interior or exterior brake resistance. 690 V grade
haven’t build-in brake unit .
DC brake
Optional start-up and stopaction frequency 0~15Hz
action volt. 0~15%action time 0~20.0 s
Jog
Jog frequency range: 0.50Hz~50.00Hz; jog
accelerating decelerating time 0.1~60.0s can be set
Multisection speed running Realized by interior PLC or control terminal
Interior PID controller Be convenient to make closed-loop system
Automatic energy save running
Optimize V/F curve automatically based on the load
to realize power save running
Automatic volt. regulation
(AVR)
Can keep constant output volt. When power source
voltage varies.
Automatic current limiting
Limit running current automatically to avoid
frequent over-current which will cause trip
Running
function
Running order specified channel
Key pad specified, control terminal specified, serial
port specified.
Running frequency specified
channel
Digital provision, analog provision, impulse
p
rovision, serial port provision, combined
provisioncan be switched at any time by kinds of
method.