Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 Appendix 1 EDS1100 Drawing machine Inverter Manual
146
F5.10
Open circuit electric collector
output terminal OC1 output
setting
0:inverter running (RUN)
1:frequency arriving signal(FAR)
2:frequency level detect signal(FDT1)
3:Reserved
4:Over load warning alarm signal(OL)
5:Output frequency reach high limit(FHL)
6:Output frequency reach low limit(FLL)
7:inverter under voltage blockage stop (LU)
8:external failure stop running (EXT)
9:inverter zero speed running
10:PLC running
11:simple PLC section running finished
12:PLC finish a cycle running
13:Reserved
14:inverter ready to run (RDY)
15:inverter malfunction
16 : Swing frequency high and low limit
restriction
17:interior counter reach final value
18:interior counter reach specified value
19:set run time arriving
20:interior timing arriving
21:OC1- the first pump of variable frequency
OC2- the first pump of bypass
frequency
OC3- the second pump of variable
frequency
OC4- the second pump of bypass
frequency
22:Reserved
23:Reserved
24:Reserved
F5.15
FDT1(frequency level)
electric level
0.00-Upper limit frequency 0.01Hz 10.00Hz ○
F5.16 FDT1 lag 0.00-50.00Hz 0.01Hz 1.00Hz ○
F5.17
Analog output (AO1)selection 0:output frequency (0-high limit frequency)
1:set frequency (0-high limit frequency)
2:output current (0-2×rated current )
3:output voltage (0-1.2×load motor rated
voltage)
4:Busbar voltage (0-800V)
5:PID provision (0.00-10.00V)
6:PID feedback (0.00-10.00V)
7:Reserved
8:Reserved
9:Reserved
1 0 ○
F5.18 Analog (AO1)gain 0.50-2.00 0.01 1.00 ○
F5.19 Analog output (AO1) offset 0.00-10.00V 0.01 0.00 ○
F5.20 Analog output (AO2) selection Same as F5.17 1 0 ○
F5.21 Analog output (AO2) gain 0.50-2.00 0.01 1.00 ○
F5.22 Analog output (AO2) offset 0.00-10.00V 0.01 0.00 ○