10.3 Multi-step speed control running
10.3.1 Parameter setting
(1) Set parameter F8.01-F8.06 according to rated value of the motor.
(2) Set F0.02 parameter to 1to choose terminal run command channel.
(3) F2.30-F2.44: multi-step speed frequency setting.
(4) F5.00-F5.07 set multi-step speed terminal control function.
10.3.2 Basic wiring diagram
Fig.10-3
multi-step speed control 2
S
T
FWD
COM
TA
TC
M
U
E
motor
W
V
TB
REV
X1
X5
Y1
COM
R
forward run
reverse run
multi-ste
p
s
p
eed control 1
X2
X3
free stop
X4
L2
Failure warning light
L1
24V
PLC run indicator li
g
ht
reset
multi-step speed control 3
3 phase breaker
EDS1000
3 phase 380V
50/60Hz
(1) If F5.08=0,namely 2 wire control mode 1: FWD and COM are closedmoter is
in forward runREV and COM are closedmotor is in reverse runFWD, REV
and COM are closed or opened togetherthe inverter stop.
(2) If any one or more terminal of X1, X2, X3 and COM are closed together, the
inverter will run according to multi-step speed frequency determined by X1,
X2, X3(multi-step speed frequency set value are determined by
F2.30-F2.44).Can realize manual control and automatic control for multiple
frequency, and also control for forward run, reverse run, free stop, reset,
warning protection.
!