Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
104
6.9 Motor and vector control parameter group: F8
F8.00 Control mode setting Range: 0, 1 0
0: V/F control
Please select V/F control mode if you need to use single inverter to drive
more than one motor.
1: vector control
Sensor less vector control run mode is mainly applied to speed control, torque
control etc. which require high control performance.
F8.01 Motor rated voltage Range: 1-480V
Depend on
device type
F8.02 Motor rated current Range: 0.1-999.9A
Depend on
device type
F8.03 Motor rated frequency Range: 1.00-400.0Hz
Depend on
device type
F8.04 Motor rated speed Range: 1-9999r/min
Depend on
device type
F8.05 Motor pole quantity Range: 2-14
Depend on
device type
F8.06 Motor rated power Range: 0.1-999.9KW
Depend on
device type
Please set above parameters according to rated data of motor drived by the
inverter for the sake of safe running.
F8.07
Motor stator
resistance
Range: 0.000-9.999ohm
Depend on
device type
F8.08
Motor rotor
resistance
Range: 0.000-9.999ohm
Depend on
device type
F8.09
Motor stator
leakage inductance
Range: 0.0-999.9mH
Depend on
device type
F8.10
Motor rotor
leakage inductance
Range: 0.0-999.9mH
Depend on
device type
F8.11
Motor mutual
inductance
Range: 0.0-999.9mH
Depend on
device type