state if ineffective and run frequency is at traverse preset frequency.
LED 2
nd
bit:
0: changing traverse amplitude. Amplitude AW varies with center
frequencyfor its changing rate please see F6.02 definition.
1: fixed traverse amplitude. Amplitude AW is determined by high limit
frequency and F6.02.
changing amplitude: AW=center frequency×F6.02
fixed amplitude: AW=high limit frequency×F6.02
As shown in Fig.6-37If this parameter is set to 0, no jumping frequency.
Whole time for a cycle including traverse rising, descending process.
Define runtime of traverse rising segment=F6.04×F6.05 (s)runtime of
descending segment = F6.04× (1-F6.05) (s). Please refer to description in
Fig.6-37
F6.06 is used for defining inverter run frequency before entering into traverse
operation.
When automatic start-up mode is optionedF6.07 is used for setting holding time
running at traverse preset frequency before enter into traverse operationWhen
manual start-up mode is optionedF6.07 setting is ineffective. Please see description
in Fig.6-37.
F6.02 Traverse amplitude threshold
Range: 0.050.0(%)
0.0(%)
F6.03 Sudden jumping freq.
Range: 0.050.0(%)
0.0(%)
F6.04 Traverse cycle
Range: 0.1999.9s
10.0s
F6.06 Traverse preset frequency Range: 0.00400.00Hz 0.00Hz
F6.07
Traverse preset frequency
latency time
Range: 0.06000s 0.0s
F6.05
Triangle wave
rising time
Range: 0.098.0(%)(traverse
cycle)
50.0(%)
Traverse center frequency input setting channel is set by F0.00 function.
!
Traverse run frequency is restricted by high limit, low limit frequency if set
improperlyabnormal traverse operaion arise.
note