www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
99
Set count number provision,shows that when some number of pulse are
inputted to Xi(count triggering signal input function terminal), OC1 (open
collector Output terminal) output a indicator signal.
As shown in Fig.6-36,OC1 output an indicator signal when the 8th pulse is
inputted to Xi. Here F5.25=8.
Specified count number provision,shows that when some number of pulse are
inputted to Xi, Yi output a indicator signal,till set count number is reached.
As shown in Fig.6-36,OC2 start to output an indicator signal when the 5th
pulse is inputted to Xi. Until set count number 8 is reached. Here F5.26=5.
Specified count number is ineffective when it is bigger than set count number.
Fig.6-36 Set count number and specified count number provision
F5.27 Interior timing setting
Range: 0.1-6000.0s
60.0
This parameter is used to set timing time of interior timer of the inverter. The
timer is activated by exterior triggering end(triggering end selected by
F5.00~F5.07), the timer begins timing upon receiving exterior triggering signal,
after it’s up to timing time one effective pulse signal of 0.5s will be outputted
from relative OC end.
6.7 Traverse special function parameter group: F6
0: traverse function ineffective
1: traverse function effective
LED 1
st
bit: jump-in mode
0: automatic jump-in mode. After start-up run at traverse preset frequency
for a period of time, then enter into traverse operation automatically.
1: terminal manual run mode. When set the multifunction terminal
Xi(Xi=X1~X8)to function 32 and it’s effective,enter into traverse state;quit traverse
F6.00 Traverse function selection Range: 0, 1 0
F6.01 Traverse run mode
Range: LED 1
st
bit: 0, 1
LED 2
nd
bit: 0, 1
00
1
2
3
4
5 6
7 8
9
Xi input
OC1
OC2