F5.17 Analog output(AO1)selection
Range: 09
0
0: output frequency(0high limit frequency)
1: set frequency(0high limit frequency)
2: output current(02×rated current)
3: output voltage(01.2×load motor rated voltage)
4: bus-bar voltage(0800V)
5: PID provision (0.00-10.00V)
6: PID feedback (0.00-10.00V)
7: reserved
8: reserved
9: reserved
F5.18
Analog output(AO1)gain
Range: 0.002.00
1.00
F5.19 Analog output(AO1) offset
Range: 0.0010.00V
0.00
For AO1 and AO2 analog output, the user can modify display measuring range
or emend meter head error by adjusting output gain if necessary.
F5.20 Analog output(AO2)selection
Range: 09
0
Same as F5.17 function parameter description.
F5.21
Analog output(AO2)gain
Range: 0.002.00
1.00
F5.22 Analog output(AO2) offset
Range: 0.0010.00V
0.00
Same as F5.18 and F5.19 function parameter description.
F5.23
DO terminal output function
selection
Range: 0~9
0
Same as F5.17 function parameter description.
F5.24
DO max. pulse output freq.
Range: 0.120.0
(max. 20KHz)
10.0
DO port max. output pulse frequency corresponds to maximum value optioned
by F5.23for example 0: output frequencythen max. Output pulse frequency
corresponds to high limit frequency.
F5.25
Set interior count number
arrivin
g
p
rovision
Range: 09999
0
F5.26
Specified interior count
number arrivin
g
p
rovision
Range: 09999
0
F5.25, F5.26 is supplementary definition to No. 17, 18 function in Table 6-8.
This function makes real-time effect to analog output when it’s being modified.
note