Owner`s manual

19
4.
Problem: Excessive dirt accumulation surrounding air registers in the home.
Possible Causes:
Remedies:
Furnace is not connected to
return air duct and is drawing
dirt from furnace room oor and
disbursing it throughout home.
Connect to return air duct system.
Install lter box on furnace. Install lter in lter box.
Filter box not installed, or no lter
in lter box.
5.
Problem: Smoke from the re chamber is pufng back through the draft control.
Furnace is not connected to
return air and is drawing smoke
fumes from the ue.
Connect to return air duct system. Or room may be too airtight, refer
to “Location and Installation” section on page 3.
Possible Causes:
Remedies:
Excessively long run of stove
pipe from furnace to ue.
Relocate the furnace so the horizontal run does not exceed 5 feet
and has a 2 inch rise per foot.
The run should not contain more than 2 elbows.
Replace with a larger ue providing a minimum of 50 square
inches but not more than 100 square inches of draft area. If the
ue is within these specications, check the draft with a draft gage
(manometer). Your ue should provide a minimum of .04 water
column inches and a maximum of .08 water column inches.
Too many elbows.
Insufcient ue size.
6.
Problem: Flames discharging from fuel door during reloading.
Opening the door has provided
additional oxygen which has
ignited the accumulated gases
from partially spent fuel.
Always open the door cautiously and allow the safety latch system
to perform its designed function, containing gases within the re
chamber.
Possible Causes:
Remedies:
Open damper.
Cast iron damper in the
“CLOSED” position.
Insufcient natural draft or an
obstruction in the ue system.
See #6 and #9.
Fire chamber lled to capacity
with unburned fuel.
Do not attempt to overload the furnace.