Installation Instructions

12
CRI 105 - STANDARD For INSTALLATION of RESIDENTIAL CARPET
Copyright © 2019 by The Carpet and Rug Institute, Inc.
General Requirements
Before direct glue-down, double-glue down and free floating carpet tile systems, the owner
or general contractor, or their designated testing agent, is required to submit to the flooring
contractor a written report on the moisture and alkalinity conditions of the concrete
substrates.
Refer to the manufacturer’s written instructions for guidelines regarding allowable moisture
and pH limits for their products. The Moisture Vapor Emission Rate, Relative Humidity &
Alkalinity testing must be performed to give an accurate assessment of the concrete
condition and the test results/data of each test shall be within acceptable limits.
Proper testing is essential for a successful installation and any deviation from these
industry accepted test methods often results in an installation failure and may void
manufacturers’ warranties.
NOTE: It is recommended that qualified independent third-party testing agencies be used for
determining moisture and alkalinity conditions of a concrete slab. Testing by an independent
third party specialist to determine installation suitability is a prudent and necessary safeguard
for general contractors, owners, architects, flooring product providers and installation
contractors to reduce the risk of concrete slab moisture related flooring problems. As a
minimum, testing agencies or individuals are required to demonstrate verifiable experience in
concrete moisture testing or be certified by a recognized organization.
6.1
Moisture Vapor Emission Rate (MVER) Testing
MVER tests must be conducted in accordance with the current version of ASTM F 1869, not
to exceed manufacturer’s requirements (ASTM F1869 - Standard Test Method for Measuring
Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride).
6.2
Relative Humidity (RH) Testing
Testing for internal relative humidity of concrete slabs must be conducted in accordance with
the current version of ASTM F2170, not to exceed manufacturer’s requirements (ASTM F2170
- Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using In-
Situ Probes).
6.3
Testing for Alkalinity
Testing the pH at the surface of a concrete slab must be conducted in accordance with the
current version of ASTM F710, not to exceed manufacturer’s requirements (ASTM F710 -
Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring).
NOTE: Preparing the surface of a concrete slab for pH testing can be problematical. Make
sure the concrete surface is adequately cleaned of adhesives, curing compounds etc. When
pH readings are less than 7, it may be an indication of a residue remaining on the concrete