User guide
14
1.5.1.3 Other Fuels
The detector reacts to other types of fire as follows:
• The baseline fire refers to n-heptane 1ft
2
(0.1m
2
) and is defined as 100% sensitivity.
• For fuel fire – standard pan fire size: 1 ft
2
(0.1 m
2
).
• For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.
• Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Type Of Fuel
Percent of Max. Distance at each Sensitivity
Range
Gasoline
100%
N-Heptane
100%
JP4 70%
Kerosene 70%
Diesel Fuel 70%
Alcohol 95% 60%
IPA 60%
Methanol 55%
Methane 45%
LPG 45%
Paper 35%
Polypropylene 15%
1.5.2 Cone of Vision
• Horizontal: 100°
Figure 1: Horizontal Field of View