USER GUIDE Ref : NP40IGB REV A – Nov 2009
GAS DETECTION We are delighted that you have chosen an INDUSTRIAL SCIENTIFIC instrument and would like to thank you for your choice. We have taken all the necessary measures to ensure that your instrument provides total satisfaction. Now it is important to read this document carefully.
About this Guide This guide describes the SharpEye Model 40/40I Triple IR (IR3) Flame Detector and its features and provides instructions on how to install, operate and maintain the detector. This guide includes the following chapters and appendixes: • Chapter 1, Introduction, provides a general overview of the product, principles of operation, and performance considerations.
Abbreviations and Acronyms Abbreviation Meaning ATEX Atmosphere Explosives AWG BIT American Wire Gauge Built In Test EMC Electromagnetic Compatibility EOL End of Line FOV Field of View HART Highway Addressable Remote Transducer-communication protocol IAD Immune at Any Distance IECEx IPA International Electrotechnical Commission Explosion Isopropyl Alcohol IR Infrared JP4 Jet Fuel Latching Refers to relays remaining in the ON state even after the ON condition has been removed LED Lig
Table of Contents About this Guide ........................................................................................................................ 4 Abbreviations and Acronyms ...................................................................................................... 5 1 INTRODUCTION.................................................................................................................9 1.1 Overview ................................................................................
3 OPERATING THE DETECTOR .......................................................................................31 3.1 Powering Up ................................................................................................................ 31 3.2 Safety Precautions ........................................................................................................ 31 3.2.1 Default Functions Settings ..................................................................................... 32 3.
List of Figures Figure 1: Horizontal Field of View ................................................................................................................................. 14 Figure 2: Vertical Field of View...................................................................................................................................... 15 Figure 3: Indication LED: Indication LED ....................................................................................................................
1 INTRODUCTION 1.1 Overview The SharpEye 40/40I is a flame detector that utilizes improved IR3 technology to provide state-of-the-art fire protection. The 40/40I uses patented digital signal processing to analyze the spectral and dynamic characteristics of the infrared radiation, to identify fire events with exceptional sensitivity and extreme immunity to false alarms. All 40/40 series detectors include a heated optical window for improved performance in icing, snow and condensation conditions.
40/40I X X X X X Ex Approval F – FM / CSA C - ATEX / IECEx Housing S - Stainless Steel A - Aluminum Electrical Entries 1 - M25 2 - ¾" NPT Temperature 1 - 75°C 2 - 85°C Wiring Configuration See Table 1 Table 1 describes the wiring options in detail. Table 1: Wiring Options Wiring Option Connections Provided 1 Power Manual BIT Fault Relay N.C Alarm Relay N.O 4-20mA Sink RS-485 2 Power Manual BIT Fault Relay N.O Alarm Relay N.
1.3 Features and Benefits • • • • • • • • • • • • • Detection Range: Up to 215 ft (65m) for a 1 ft2 (0.1m2 ) n-heptane fire. Ultra High Immunity to False Alarms. Advanced Digital Processing of the Dynamic Characteristics of Fire: Flickering, threshold correlation and ratio. Multi IR Channels: Between 3-5 microns Field Programmable Sensitivity: Four ranges to avoid zone crossover. Built In Test (BIT): Manual and Automatic (see Built-In-Test (BIT) on page 19).
The heated optics can be set to one of the following: • Not operated • On continuously • Automatic, per temperature change (default): you can define the start temperature below which the window is heated. (The default is 68°F (20°C).) This temperature can be defined between 32°F (0°C) to 122°F (50°C). The heating stops when the temperature is 27°F (15°C) above the start temperature. For more information, see Configuring your Detector on page 29. 1.4.
1.4.5.3 SIL-2 Approved The 40/40I Flame Detector is certified to SIL-2 requirement per IEC 61508.4, Chapter 3.5.12. The alert condition according to SIL-2 can be implemented by: • Alert signal via 0-20mA current loop. or • Alert signal via alarm relay and fault relay. • For more details and guidelines for configuring, installing, operating and service – see SIL-2 Features on page 48 and TÜV Report No. 968/EZ326.00/008. 1.4.5.4 EN54-10 The 40/40I Flame Detector is certified to EN54-10 and CPD.
1.5.1.3 Other Fuels The detector reacts to other types of fire as follows: 2 2 • The baseline fire refers to n-heptane 1ft (0.1m ) and is defined as 100% sensitivity. 2 2 • For fuel fire – standard pan fire size: 1 ft (0.1 m ). • For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire. • Maximum Response Time: 10 sec. Table 3: Fuel Sensitivity Ranges Type Of Fuel 1.5.2 Percent of Max.
• Vertical: +50° (down) , -45° (up) Figure 2: Vertical Field of View 1.5.3 False Alarms Prevention To prevent false alarms, the detector will not alarm or react to the radiation sources specified in Table 4.
Quartz lamp (1000 W) Mercury vapor lamp Grinding metal Lit cigar Lit cigarette Match, wood, stick including flare up >3 (1) IAD IAD >1 (0.3) >1 (0.3) >10 (3) Notes: IAD = Immune at Any Distance. • All sources are chopped from 0 to 20 Hz. • Table 5: Welding Immunity Distance Sensitivity Setting 1.5.4 Detection Range Immunity Distance 1 50 ft (15m) >6 ft (2m) 2 100 ft (30m) >12 ft (4m) 3 150 ft (45m) >17 ft (6m) 4 215 ft (65m) >25 ft (7.
1.5.5 Output Signals Outputs are available according to the default configuration or the wiring options selected for the 40/40I IR3 Detector. Determine the outputs for your model according to table 7 The detector incorporates several types of output suitable to different control systems: • 0-20mA (stepped) with HART • Relays (Alarm, Fault, Auxiliary) • RS-485 Modbus Table 7: Available Output Types Output Type Alarm relay Auxiliary relay Fault relay 0-20mA current output RS-485 1.5.
Table 9: Output Signals ve rsus Detector State Detector State LED Indicator Normal Green LED Mode Alarm Relay 1Hz Off Auxiliary Relay Off (4) mA output On 5 mA On 10 mA Warning Red 2Hz Off (1) Red Constant On On On 15 mA Red Constant On Off On(4) On On 15 mA 15 mA Yellow 4Hz Off Off Off 2 mA Off 10 mA Alarm (2) Latch BIT Fault (3) On Fault Relay (4) Warning at BIT Fault Red 2Hz Off Alarm at BIT Fault Red Constant On On Off 15 mA Yellow 4Hz Off Off
1.6 Internal Detector Tests The detector performs two types of self tests: • Continuous Feature Test, page 19 • Built-In-Test (BIT), page 19 1.6.1 Continuous Feature Test During normal operation, the detector tests itself continuously and indicates a fault if a failure is found. This type of test complies with SIL-2 requirements.
1.6.2.1 How the BIT Operates • The detector's status remains unchanged if the result of a BIT is the same as the current status (NORMAL or BIT Fault) • the detectors’ status is changed (from Normal to BIT Fault or vice versa) if the BIT differs from the current status Note: In ‘BIT Fault’ status the detector can continue to detect a fire. 1.6.2.2 Automatic BIT The detector automatically performs a BIT every 15 minutes. A successful BIT sequence does not activate any indicator.
Table 12: Results of a Successful Manual BIT Output FAULT relay Result • Wiring options 1, 2, and 4: remains CLOSED (Normal) • Wiring options 3 and 5: remains OPEN (Normal) ALARM relay Activated for 3 sec (only when the function Alarm BIT is set to YES) AUXILIARY For wiring options 4 and 5: is activated for 3 sec (only when the relay function Auxiliary BIT is set to YES) 0-20mA output Wiring option 1, 2, 3: • Initiates 15 mA only when the function Alarm BIT is set to YES • Initiates 10 mA when the function
• Environment: • Dust, snow or rain can reduce the detectors sensitivity and require more maintenance activities. • The presence of high intensity flickering IR sources may affect sensitivity. • Aiming the Detector: • The detector should be aimed toward the center of the detection zone and have a completely unobstructed view of the protected area. • Whenever possible, the detector face should be tilted down at a 45º angle to maximize coverage and prevent accumulation of dust and dirt.
2.4 Certification Instructions Warning: Do not open the detector, even when isolated, when flammable atmosphere present. Use the following certification instructions: • The cable entry point may exceed 167°F (75°C). Suitable precautions should be taken when selecting the cable. • The equipment may be used with flammable gases and vapors with apparatus groups IIA and IIB + H2: • T5 in the ambient temperature range: –67°F (–55°C) to +167°F (+75°C).
• • • • 2.6 When using the optional tilt mount, use flexible conduits for the last portion connecting to the detector. For installations in atmospheres as defined in group B of the NFPA 72E, seal the conduits inlets. When pulling the cables through the conduits, ensure that they are not tangled or stressed. Extend the cables about 30 cm. (12 in.) beyond the detector location to accommodate wiring after installation.
2.6.1 Tilt Mount Specifications Table 15: USA Version Item Qty Type Location Tilt Mount 1 40/40-001 Screw 4 ¼" 20 UNC x ¾" Detector – Holding plate Spring Washer 4 No. ¼" Detector - Holding plate Location Table 16: European Version 2.6.2 Item Qty Type Tilt Mount 1 40/40-001 Screw 4 M6 x 1 x 20 mm Detector – Holding plate Spring Washer 4 M6 Detector - Holding plate Tilt Mount Assembly Figure 5 shows the Tilt Mount Assembly.
Figure 6: Tilt Mount Assembly (dimensions in mm and inches) Ø To install the Tilt Mount and Detector: 9 Place the tilt mount in its designated location and secure it with four (4) fasteners through four (4) holes 7 mm in diameter. Use the 4 screws and spring washers according to the kit (see 10 Table 15 and 11 Table 16 ). Note: Removing the detector for maintenance purpose does not require the Tilt Mount to be removed). 12 Unpack the detector.
2.7 Connecting the Detector This section describes how to connect the electric cabling to the detector (Figure 7). Ø To connect the detector to the electrical cables 15 16 17 18 Disconnect the power. Remove the back cover of the detector by removing four (4) socket head-screws in the cover bolts. The terminal chamber is now revealed. Remove the protective plug mounted on the Detector Conduit/Cable entry; pull the wires through the Detector Inlet.
2.7.1 Verifying the Detector Wiring The detector has five output wiring options within the EExde integral terminal section of the enclosure. There are 12 terminals labeled 1-12. Table 17 describes the function of each terminal for all the wiring options. Table 17: Model 40/40I Wiring Options Wire Terminal No.
2.8 Configuring your Detector You can reprogram the function setup using the RS-485 connection or using the Hart Protocol as follows: • Industrial Scientific Host Software : The Industrial Scientific Host Software is for use on a PC or laptop. Refer to Manual TM777050 for programming instructions. The Host software enables you to change the functions. • Handheld Unit: Refer to Manual 777060 for programming instructions when using the Handheld Unit.
2.8.2 Alarm Delay The detector is equipped with an Alarm Delay option, which provides programmable time delays with settings at: • Antiflare* (default) *The Antiflare mode is selected to prevent false alarms in locations where fast flares may be present. The Time Delay for fire alarms in this mode ranges from 2.5 to 15 seconds (usually, less than 10 seconds).
2.8.5 Heated Optics The heated optics can be defined as one of the following modes: • Heated Mode • OFF: Not operated • On: Continuously • AUTO: Per temperature change In AUTO mode, the default HEAT ON setting is 68°F (20°C). Heating stops when the temperature is 27°F (15°C) above the start temperature. You can define the start temperature below which the window will be heated. The temperature can be defined between 32°F and 122°F (0°C to 50°C).
3.2.1 • You should only access the wiring compartment to wire or remove the detector or access RS485 terminals for maintenance. • Disconnect or disable external devices, such as automatic extinguishing systems before carrying out any maintenance. Default Functions Settings Table 20 lists the default function configuration supplied with the detector.
3.3.1 Automatic BIT Test Check that the indicators show normal conditions. See Powering Up on page 31. 3.3.2 Manual BIT Test Important: If the function setup Alarm BIT and/or Auxiliary BIT are set to Yes (default No), the Alarm, Auxiliary Relay and 0-20mA outputs are activated during a Manual BIT. Therefore, automatic extinguishing systems or any external devices that may be activated during BIT must be disconnected. Ø To perform a Manual BIT: 27 28 3.3.3 Verify that the detector is Normal Mode.
4 MAINTENANCE AND TROUBLESHOOTING This chapter deals with preventive maintenance, describes possible faults in detector operation and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty. Whenever a unit requires service, please contact Industrial Scientific or its authorized distributor for assistance. 4.
4.1.3 Keeping Maintenance Records It is recommended that maintenance operations performed on a detector are recorded in a Log-book. The record should include the following: • Installation date, and contractor • Serial and tag no. • Entries for every maintenance operation performed, including the description of the operation, date and personnel ID. If a unit is sent to Industrial Scientific or a distributor for service, a copy of the maintenance records should accompany it. 4.
Appendices 36
A Technical Specifications A.1 Electrical Specifications Operating Voltage Power Consumption Electric Input Protection Electrical Interface Electrical Outputs 18-32 VDC • Without Heated Optic: Max. 100 mA in Standby Max. 150 mA in Alarm • With Heated Optic: Max. 150 mA in Standby Max. 200 mA in Alarm The input circuit is protected against voltage-reversed polarity, voltage transients, surges and spikes according to MIL-STD-1275B. There are five output-wiring options.
• • * In wiring options 3, 5 the relay is normally energized open during normal operation of the detector. The relay is de-energized close contact if a fault condition or low voltage situation occurs. 0-20mA Current Output: The 0-20mA can be Sink or Source according to the wiring option source (see General Instructions for Electrical Wiring on page 40). The maximum permitted load resistance is 600O. Table 24: 20 mA Current Output State Output Fault 0 + 0.
A.2 Mechanical Specifications Enclosure Stainless Steel 316 or Aluminum, heavy duty copper free (less than-1%), red epoxy enamel finish Hazardous Area Approvals • FM, CSA Class I Div. 1 Groups B, C and D; Class II/III Div. 1 Groups E, F and G. ATEX, IECEx ; EX II 2 GD, EExde IIB + H2 T5 (75°C), T4 (85°C) NEMA 250 type 6p. IP 66 and IP 67 per EN 60529 • Water and Dust Tight • • Electronic Modules Electrical Connection (two entries) A.
• Dust • • Vibration • Mechanical Shock • • Electromagnetic Compatibility (EMC) Designed to meet MIL-STD-810C, method 510.1, procedure I Exposure to a dust concentration of 0.3 frames/cubic ft. at a velocity of 1750 fpm, for 12 hours Designed to meet MIL-STD-810C, method 514.2, procedure VIII Vibration at an acceleration of 1.1g within the frequency range of 5-30 Hz, and an acceleration of 3g within the frequency range of 30-500 Hz Designed to meet MIL-STD-810C, method 516.
36 Use Table 26 to select wire gauge for power supply wires. DO NOT connect any circuit or load to detectors’ supply inputs. • Select Number of detectors connected in one circuit. • Select wiring Length per your installation requirements. • Refer to Power Supply Range for voltage extreme applied.
Table 27: Wiring Connections Wiring Option Detector Model Terminals 5 8 9 1 40/40I-1XXXX Fault Relay (N.C) 0-20mA (Sink) 0-20mA (Sink) 2 40/40I-2XXXX Fault Relay (N.C) Alarm Relay (N.C) 0-20mA Duct Source 3 40/40I-3XXXX Fault Relay (N.O) Alarm Relay (N.C) 0-20mA Duct Source 4 40/40I-4XXXX Fault Relay (N.C) Auxiliary Relay (N.O) Auxiliary Relay (C) 5 40/40I-5XXXX Fault Relay (N.O) Auxiliary Relay (N.
Figure 11: 0-20mA Wiring (Source) 3-Wire Connection Notes: The detectors are supplied as: • Isolated 0-20mA – Sink in wiring option 1. • As non-isolated 0-20mA – Source in wiring options 2 and 3. • There are no 0-20mA outputs in wiring options 4 and 5. C RS-485 Communication Network C.
D Accessories This appendix describes the accessories that can help you maximize fire detection with the SharpEye IR3 flame detector: D.1 Long Range IR3 Fire Simulator (Ref 6798433° The SharpEye IR3 Long Range Fire Simulator 20/20-310 is designed specifically for use with SharpEye IR3 flame detectors. The Fire Simulator emits IR radiation in a unique sequential pattern corresponding to and recognizable by the IR3 detector as fire.
Ø To simulate a fire: 37 Aim the Fire Simulator towards the detector’s Target Point. Target Point Figure 14: 40/40I IR3 Detector Target Point 38 39 40 41 D.1.3 When testing keep a distance of at least 50 cm (20 inches) from the detector. Press the operation button once. Fire simulation lasts for 20 seconds. The detector sends an alarm signal (solid red LED). Wait 20 seconds before repeating the test. Verify that the optical window is clean.
46 47 D.1.5 Charge for a maximum of 14 hours. Disconnect the charger. Tighten the sealed plug clockwise. Technical Specifications Mechanical • • • • • • Electrical • • • • Environment • • • Physical • • D.2 Explosion Proof Enclosure: NFPA (designed to meet) Class I, Division 1 & 2 Groups B, C and D Class II, Division 1 & 2 Groups E, F and G ATEX EX II2G NEMKO 02ATEX255 EExd IIB T5 50°C per En 50-014 & EN50-018 Power: 8 VDC Max. 6 x Rechargeable 1.2 VDC NiCd Batteries Current: 2.5A Avg.
D.3 Weather Protection – '(Ref B103908) The weather protector protects the detector from different weather conditions, such as snow and rain. Figure 16: Weather Protection D.4 Laser Detection Coverage Pointer - P/N 777166 The Laser Detection Coverage Pointer evaluates detector coverage on-site. The device is an add-on accessory that enables designers and installers to optimize detector location and assess the actual coverage of installed detectors.
D.5 Air Shield - P/N 777161 The Air Shield enables you to install the detector in dirty areas and using compressed air, keep the window clean. This prevents the accumulation of dirt on the window and enables the detector to continue to operate under harsh conditions. Figure 18: Air Shield E SIL-2 Features E.1 40/40I Flame Detector This appendix details the special conditions to comply with the requirements of EN 61508 for SIL 2.
E.1.2 Guidelines for Configuring, Installing, Operating and Service The alert conditions according to SIL 2 can be implemented by an: • Alert signal via 20mA current loop or • Alert signal via alarm relay and the fault relay E.1.2.1 Conditions for Safe Operating 48 The flame detector shall consist only of the approved hardware and software modules. 49 The 24V power supply must fulfill the requirements for PELV / SELV of EN 60950. 50 The automatic BIT (Built-In-Test) must be activated.
50
51