Instruction manual
4 
1.3 Heater Suspension 
1.3.1 First considerations 
•  Clearances from combustibles must be 
maintained. (See figure 2) 
•  For ease of servicing there should be a   
minimum clearance distance of 500mm 
between the burners of the heating system 
and the building wall. This measurement 
can be reduced for perimeter type systems. 
(See figure 1a). 
•  For ease of servicing and burner removal 
minimum clearances should be maintained. 
(See figure 1b and 1c). In exceptional    
circumstances the burner lid may be slid 
diagonally for removal thus reducing the 
vertical distance. 
•  Ensure that the suspension is sufficiently 
flexible to allow for thermal expansion. 
1.3.2 Suspending the heater - General 
1.3.2.1  The first support is always positioned at 
the support lug suspension point on the end 
vent burner combustion chamber. 
1.3.2.2  Subsequent  supports  are  placed 
approximately 2.8m apart, including one at each 
combustion chamber location. This gives a max-
imum load per support of 24kg. 
1.3.2.3 A support must always be located at a        
maximum distance of 2m from a tee or elbow 
fitting. 
1.3.2.4  Except for the combustion chamber   
support lug suspension points, suspension   
support brackets are installed to support the 
tube  section  which  is  then  covered  with 
reflectors. 
1.3.2.5  Tail pipe hangers are installed for the 
tube section which will be without reflectors. 
If there are any doubts as to the strength or     
suitability of roof steelwork to which heaters are 
to be suspended, please refer to a Consultant, 
Architect or owner of the building. 
Table 1. Minimum mounting heights 
Model 
Minimum Mounting 
Heights (m) 
NRV12LR 
3.0m 
NRV18LR 
3.6m 
NRV24LR 
4.0m 
NRV32LR 
4.7m 
NRV38LR 
5.3m 
NRV46LR 
6.0m 
(100mm MIN - Perimeter Systems) 
A - Burner Tube 
B - LR Burner 
C - Optional Perimeter Reflector 
D - Wall 
Figure 1.a Overall Dimensions 










