Unit installation

WATER FLOW SWITCH INSTALLATION
Plumb the optional water FLOW switch externally on the water
"in" piping. Position the flow switch on the water "in" line so it
only detects the water flow through the unit itself.
Remove the existing leads from the water PRESSURE switch.
Then connect them to an insulated two pair cable with 14 to 12
gauge wire.
Run the cable from the flow switch to the inside of the units cabi-
net and wire accordingly. Make sure all connections are water
tight. Use the proper slip connectors. Leave the existing water
pressure switch in place or remove and replace with a 1/4 inch
machine threaded "copper" or "p.v.c." plug. Use teflon tape and
pipe sealer.
Start the circulation pump and heater. Adjust the set screw
counter
clockwise until the unit shuts off. Then turn the set screw clock-
wise until the unit starts, then add three more turns clockwise.
Test run all equipment that may slow the water flow and readjust
as needed. Make sure the heater shuts off when the circulation
pump does.
19
Gauge
In most cases the existing water pressure switch located
inside the access compartment can be changed to this spe-
cial use water pressure switch. This water pressure switch
can be set at a higher rating to offset the static pressure in
some cases. The factory part number is #408. Install this
switch in place of the existing water pressure switch when
needed. If it does not solve the static pressure problem then
use the optional Gridâ„¢ flow switch. The factory part num-
ber is #888-032.
See "Water Pressure Switch" for more information re-
garding the water pressure switch.