42 Rockwell Automation Publication PFLEX-IN020C-EN-P - July 2013
PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures
700S Control Connections
1. To access the ASIC board(s), remove the front protective cover(s) from
the power structure(s) as shown below.
2. Connect the 24V power supply cable and the fiber optic cables between
the Voltage Feedback Board and the Common Mode Filter and Fiber
Optic Interface or Fiber Optic Star Interface boards. Refer to Ta b l e 2 2
below for cable designations and connection points and figures 28
, 29, 30
and 31
for connector locations.
Complete fiber optic cable connections after all electrical wiring has
been completed to avoid damage to the cables.
Ensure that the fiber optic cables do not contact sharp objects that can
cause damage to the cables.
The fiber optic cables have a minimum bending radius of 50 mm (2.0
in.).
Table 22 - Voltage Feedback Board Cable Designations
IMPORTANT
Verify correct cable/connector placement. Connecting the wires incorrectly
could damage components.
Connect this Point … to this Point …
Location Connector Location Connector
Voltage Feedback Board J8 Common Mode Filter Board J5
J5 Fiber Optic Interface or Fiber
Optic Star Interface Board
J7
J4 J6
Frames 13 and 14
Frames 10…12
(Frame 10 shown)
Protective
Covers