Specifications
28 Rockwell Automation Publication PFLEX-IN020C-EN-P - July 2013
PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures
Table 15 - 690V AC Input Protection Devices
Drive Catalog
Number
Frame
kW Rating Input
Ratings
Dual Element Time Delay Fuse Non-Time Delay Fuse Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND HD Amps Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.
20xF261 10 250 – 263 350 575 350 775 170M5813 750 350
– 200 210 275 450 275 600 170M5813 600 300
20xF325 10 315 – 327 425 725 425 950 170M5813 900 450
– 250 263 350 575 350 775 170M5813 750 400
20xF385 10 355 – 388 500 850 500 1100 170M5813 1100 500
– 315 327 425 725 425 950 170M5813 900 450
20xF416 10 400 – 419 525 900 525 1200 170M5813 1200 550
– 315 327 425 700 425 950 170M5813 900 450
20xF460 11 500 – 463 600 (1 per phs)
300 (2 per phs)
1000 600 (1 per phs)
300 (2 per phs)
1300 170M8547 1300 600
– 400 388 500 (1 per phs)
250 (2 per phs)
850 500 (1 per phs)
250 (2 per phs)
1100 170M8547 1100 500
20xF502 11 560 – 506 650 (1 per phs)
325 (2 per phs)
1100 650 (1 per phs)
325 (2 per phs)
1500 170M8547 1500 650
– 500 463 600 (1 per phs)
300 (2 per phs)
1000 600 (1 per phs)
300 (2 per phs)
1300 170M8547 1300 600
20xF590 11 580 – 594 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
– 500 506 650 (1 per phs)
325 (2 per phs)
1100 650 (1 per phs)
325 (2 per phs)
1500 170M5813 1500 700
20xF650 12 630 – 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
– 560 594 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
20xF750 12 710 – 756 950 (1 per phs)
475 (2 per phs)
1600 950 (1 per phs)
475 (2 per phs)
2200 170M5813 2200 1000
– 630 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20xF820
(1)
12 800 – 826 1100 (1 per phs)
550 (2 per phs)
1800 1100 (1 per phs)
550 (2 per phs)
2400 170M5813 2400 1100
– 630 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20xF920 13 900 – 927 1200 (1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M6466
(5)
2700 1200
– 800 826 1100 (1 per phs)
550 (2 per phs)
1800 1100 (1 per phs)
550 (2 per phs)
2400 170M6466
(5)
2400 1100
20xF1K0 13 1000 – 1038 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
– 900 927 1200 (1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M6466
(5)
2700 1200
20xF1K1 13 1100 – 1189 1500 (1 per phs)
750 (2 per phs)
2600 1500 (1 per phs)
750 (2 per phs)
3500 170M6466
(5)
3500 1500
– 1000 1038 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
20xF1K5 14 1500 – 1511 1900 (1 per phs)
650 (3 per phs)
3300 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
– 1300 1310 1700 (1 per phs)
575 (3 per phs)
2900 1700 (1 per phs)
575 (3 per phs)
3900 170M6466 3900 1700
20xF1K9
(2)
14 1800 – 1914 2400 (1 per phs)
800 (3 per phs)
4200 2400 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
– 1500 1511 1900 (1 per phs)
650 (3 per phs)
3200 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
20xF2K2
(2)
14 2000 – 2267 2900 (1 per phs)
950 (3 per phs)
5000 2900 (1 per phs)
950 (3 per phs)
6700 170M6466 6700 2900
– 1800 1914 2400 (1 per phs)
800 (3 per phs)
4200 2400 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
(1) 20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2) Not available with 700S Control.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection.
(5) These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6) Inverse time breaker. Ratings shown are maximum.
(7) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.