Technical data
28
BALMORAL SUPERFILL
TM
Fuel oil storage and dispensing
Superfill tanks and fuel delivery systems are designed to
store and deliver fuel oil (A2) and diesel (D) to BS2869,
and up to 7% mixture biofuel to BSEN14214 standards.
Regulations and guidelines
The following regulations and guidelines are applicable to
the installation and maintenance of fuel delivery stations
and fuel oil tanks and are available from their respective
authorities:
Q
British Standards: BS5410-1/2
Q
Environment Agency: PPG2
Q
Scottish Environmental Protection Agency: PPG2
Q
OFTEC: TI/131, TI/136, T19, T32, T14
Q
Control of Pollution (oil storage) (England)
Regulations 2001
Q
Water Environment (oil storage) (Scotland)
Regulations 2006
Q
Groundwater Regulations 1998
Q
Local Building Regulations may also cover the site
preparation and installation of integrally bunded tanks.
Electrics
There is a double pole isolator switch mounted on the pump
plate inside the cabinet for connection to a mains power
source.
Filling the Superfill
Superfills can be filled from ground level through a 2"BSP
filling port. The 5000, 7500 and 10,000 litre models have a
non-return valve to minimise drips when uncoupling after
filling. (A non-return valve is not required on the HB1135,
HB2500, HB3500, VB1300 and VB2500 models).
On the 5000, 7500 and 10,000 litre models, a lever-
controlled ball valve is included for additional safety.
The Superfill's fill line has a mechanical overfill prevention
valve (OPV). The OPV limits are indicated on a label fixed
inside the cabinet door.
CAUTION
THIS TANK HAS AN OVERFILL
PREVENTION VALVE FITTED.
Min Flow Rate 50 LPM
Max Flow Rate 580 LPM
Min Pressure 0.15psi / 10mBAR
Max Pressure 100psi / 7BAR
Drainage of line 20-30 SECʼS PER M
New pics of Superfillʼs
Superfill tank features
Q
Suitable for commercial, industrial and
agricultural applications
Q
Horizontal and vertical models
Q
Refuelling components easily accessible from ground level
Q
Mechanical overfill prevention valve
Q
Capacity measurement options
Q
Self contained lockable cabinet provides additional
storage of 'incidentals'
Q
Cabinet mounted lamp
Q
Full reach 4 or 6m delivery hose - dependent on model
Q
Integral lifting points
Q
Ultra compact sizes
All Superfill tanks are supplied with a 240V pump with nozzle,
holder, hose, non-return valve, remote level gauge, bund
alarm and 2”BSP connection with cap and chain. (A non-
return valve is not required on the HB1135, HB2500, HB3500,
VB1300 and VB2500 models).
Vertical 2500, 5000, 7500 and 10,000 litre models are
supplied with 6m hose, cabinet light and cabinet mounted
analogue flowmeter.
Horizontal 1135, 2500, 3500 and vertical 1300 litre models
are supplied with 4m hose.
Superfill tanks are not suitable for the storage of kerosene
(paraffin) unless an appropriate IP rated pump is fitted.