4.3.2 Maintenance schedule for safety devices
No. Component / Maintenance Operation Int.
1 System pressure
Check the system pressure on the pressure gauge
The value must be 20% over the pre-stressed pressure of the ex‐
pansion tank
NOTICE! See the expansion tank operating instructions
If the system pressure is less:
Top up the water
If this occurs frequently it indicates that the heating system is not
sealed correctly.
Call the installer.
If large pressure fluctuations are observed:
Have the expansion tank checked.
D
2 Burn back flap
Check the seal and efficiency of the burn back flap
W
3 Safety valve (provided by the customer)
Check the safety valve as per the manufacturer's instructions
NOTICE! See the safety valve operating instructions
M
4 Safety battery valve
Pull the safety valve sensor out of its immersion sleeve
Hold the sensor in a heated water tank fitted with a temperature dis‐
play
Heat the water until the temperature reaches the setpoint value for the
valve
At this temperature the valve must open and allow cold water to
flow into the safety battery
After the test, push the valve sensor back into its immersion sleeve
Check for water flowing out of the safety battery drain pipe
Clean or change the valve if it leaks
Risk of scaling in the safety heat exchanger
If the heat exchanger is badly scaled, the flow rate will be very low. In
this case the heat exchanger must be descaled by a specialist compa‐
ny.
Q
5 Safety temperature limiter (STL)
Pull the STL capillary sensor out of its immersion sleeve
Hold the sensor in a heated water tank fitted with a temperature dis‐
play
Heat the water until the temperature reaches the setpoint value (ap‐
prox. 100°C) for the STL
The system will shut down and a fault message will be displayed
If the system does not shut down, change the STL immediately
Reset the STL by hand:
Allow the sensor to cool down and then unscrew the cap from the STL
Reset the safety temperature limiter by pressing with a screwdriver
Y
6 Heating EMERGENCY STOP switch
Check that the heating emergency stop switch is working properly
4
Servicing
Maintenance schedule