Operating instructions
❒ Check the seal when replacing the ash removal flange
➥ Because of the high temperatures to which the screw is exposed, never re‐
move all the ash. Always leave a thin layer of ash to protect it.
Ignition (not pictured)
❒ The ignition pipe must be free
❒ Clean the photocell with a damp cloth (no detergent)
Yearly
17 Underpressure controller
❒
Disconnect the silicone tube from the differential pressure transducer
❒ Using compressed air, blow out the line in the direction of the combustion cham‐
ber to remove any deposits
❒ Reconnect the silicone tube to the "minus" nipple
18 Combustion chamber overpressure sensor
❒
Loosen the retaining screw
❒ Pull the combustion chamber overpressure sensor out of the spacer tube
❒ Clean any deposits from the sensor with a soft cloth
❒ Check that the spacer tube is clear
4
Servicing
Maintenance schedule