Operating instructions
▪ Danger of fire due to flammable materials.
No flammable materials should be stored near the boiler. Flammable objects (e.g.
clothing) must not be put on the boiler to dry.
▪
Damage due to impurities in combustion air.
Do not use any solvents or cleaning agents containing chlorine in the room where
the boiler is installed.
▪ Keep the air suction opening of the boiler free of dust.
Ventilation of the boiler room
Ventilation air for the boiler room should be taken from and expelled directly outside,
and the openings and air ducts should be designed to prevent weather conditions (foli‐
age, snowdrifts, ...) from obstructing the air flow.
Unless otherwise specified in the applicable building regulations for the boiler room,
the following standards apply for the design and dimensions of the air ducts:
ÖNORM H 5170 - Construction and fire protection requirements
TRVB H118 - Technical directives on fire protection/prevention
2.5.3 Requirements for central heating water
The following standards and guidelines apply:
Austria:
Germany:
Switzerland:
Italy:
ÖNORM H 5195-1
VDI 2035
SWKI 97-1
D.P.R. no. 412
NOTICE! Note on filling with make-up water: Always bleed the filling hose before con‐
necting, in order to prevent air from entering the system.
Note on standards
Note on standards
Safety
2
Design information
Operating Instructions TM 150/199/220 | B0310611_en 13