Product manual

Installation
3-24
Part 1105120-01
E 2013 Nordson Corporation
Table 3-5 Power Supply Configuration Settings
Display Function Configuration 1 Configuration 2
ID 00..15
(Unit ID)
Unit ID: Sets unit ID for
network, identifies master
or remote.
Master = ID 00 Remotes = ID 01..15
For a standalone system controller, set the unit ID to 00. For networked power
supplies, set the master to 00 and set the remotes to 01, 02.....15.
S Each system controller on a network must have a unique ID number.
FLT
(Fault)
Fault State: Sets Unit Fault
to fault units separately or
all together.
FLT U = FAULT UNIT
(Fault this unit only)
FLT A = FAULT ALL
(Shuts down all units on
the network).
This setting is for multiple system master/remote networks. A networked system
controller in a fault condition can fault just itself or the entire network.
S All networked system controllers must have the same fault setting.
RFD
(RF Detector)
Sets RF detector status for
each system controller.
RFD Y = RF Detector
connected
RFD N = No RF detector
connected
A Master controller is automatically set to RFD Yes. Remote power supplies can be set
to Yes or No. Only one RF detector is required for a network.
NT
(Network)
Specifies network
communication protocol.
NT CAN = CAN BUS
protocol
NT 485 = 485 protocol
The CAN BUS protocol is the preferred protocol for system controller networks.
It must be selected for any network using DeviceNet.
S All system controllers on the network must be set to the same protocol.
CTRM Can termination CTRM Y = CAN
termination Yes.
CTRM N = CAN
termination No.
Internal network termination setting.
S Set to Yes for networked controllers that have only one network port connected
(and so are on one end of the network). The Master system controller is typically on
one end of the network.
S Set to No for all networked controllers that have both network ports connected.
ANA Remote Power Level
Control enable/setting
ANA Y = Y (yes) ANA N = N (no)
Refer to Table 3-3 on page 3-8 for connections.
S If set to ANA Y, then the next setting allows you to choose the input. In Remote
mode, light output is controlled by the input to the AIN and ACOM terminals
(5 and 4).
S If set to ANA N, then the light output is controlled from the system controller front
panel in both Remote and Local modes.
IN Analog input selector mA = 420 mA control V = 010 Vdc control
Specifies the input type for Remote Power Level Control. This selection appears if
ANA Y is selected. Refer to Table 3-3 on page 3-8 for connections.
CTL Remote control source IO = Use discrete remote
I/O terminal
DN = Use DeviceNet for
remote control
Refer to Table 3-3 on page 3-8 for discrete remote I/O connections. IO is the default
setting.