Product manual
Installation
3-23
Part 1105120-01
E 2013 Nordson Corporation
System Controller Configuration
Once the system controller and lamphead are mounted and all connections
made, the last step is to configure the controller for your application, using
the front panel display, keys, and configuration menus.
NOTE: The system controller power must be on and the lamphead must be
OFF to enter the configuration menus. Press the SYSTEM OFF button to
turn the lamphead off if LAMPON is displayed.
Use these keys to configure the system controller:
Key Function
Nordson Logo
(behind the letter “d”)
Press for 5−15 seconds to enter the
configuration menu.
SET−SAVE Set choice and advance to next configuration
setting.
UP/DOWN Scroll through setting choices.
MPS2-610V
SET/SAVE
UP
DOWN
NORDSON LOGO
OFF
Figure 3-17 System Controller Front Panel
1. Move the front power switch to the ON position. The system goes
through a power-up test sequence, then displays the installed software
version numbers, then displays OFF.
2. Press the Nordson Logo for 5−15 seconds to enter the configuration
menu. The configuration settings are displayed in the order listed in
Table 3-5.
3. Press the UP or DOWN keys to scroll through the choices available for
each setting. Press the SET−SAVE key to save the displayed choice
and advance to the next setting.
4. The last display is PWROFF. Turn the power supply power switch to the
OFF position to set the configuration in flash memory.
NOTE: The only configuration setting not done through the system
software is the Remote I/O Machine Stop Interlock function. Refer to
page 3-9 for this setting.