Product manual
Installation
3-9
Part 1105120-01
E 2013 Nordson Corporation
Machine Stop Interlock
CAUTION: Allow only qualified personnel to service the equipment. All
power must be disconnected. Follow the safety instructions in this document
and all other related documentation.
The Machine Stop interlock (Remote I/O pins 15 and 16) can be configured
for Normal or Isolated operation on I/O boards with the DeviceNet option by
changing the J1 and J2 jumper positions on the Remote I/O circuit board.
Jumper Position Pins Description
Normal MSTOP
(15, 16)
Input compatible looking for
contact closure only. This is the
only interlock operation mode
available on controllers without
DeviceNet.
Isolated (ISO) MSTOP
(15, 16)
External 24 Vdc @ 5 mA is
required to maintain interlock
contact closure. This is available
only on controllers with DeviceNet.
See Figure 3-7. To access the Machine Stop Interlock jumpers remove the
system controller cover. The jumpers are on the back of the I/O connector
circuit board.
S The signal voltage range for the Isolated Machine Stop Interlock is
20−30 volts DC.
S Both jumpers must be set to one of the two positions as shown in
Figure 3-7.
CAUTION: Any other jumper combination is invalid and will cause damage.
J2
J1
J2
J1
NORMAL
ISO
Figure 3-7 Machine Stop Interlock Jumper Settings − Shown Set To NORMAL