DeviceNet Specifications
10-10
Part 1105120-01
E 2013 Nordson Corporation
System Bitmap (default in bold)
Bit
Value
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
1
(ON)
Master
Faulted
Slave 1
Faulted
Slave 2
Faulted
n/a Master
Present
Slave 1
Present
Slave 2
Present
System
Ready
0
(OFF)
Master
OK
Slave 1
OK
Slave 2
OK
n/a Not
Present
Not
Present
Not
Present
Not
Ready
Instance 112 – Output Assembly 1 (Common)
Byte
Index
Description
DeviceNet
Data Type
Class
ID
Instance
ID
Attribute
ID
0 Master Lamp Command (See Notes):
1 – Off / Stop
2 – On / Start
3 – Standby
5 – Reset
USINT 0x64 0 110
1 Light Intensity Command:
20 – 100%
USINT 0x64 0 111
2 – 3 Lamp Status Select:
0: Master
115: Slaves
UINT N/A N/A N/A
NOTE: Receive_Idle condition (0 byte length message) is treated as a DeviceNet fault condition by the
CoolWave2 unit.
NOTE: Commands other than those listed are not implemented, and will be ignored by the CoolWave2
unit.
Common Services
Service Code
Implemented for
Service NameClass Level Instance Level
0E
HEX
Yes Yes Get_Attribute_Single
10
HEX
No Yes Set_Attribute_Single