DeviceNet Specifications
10-2
Part 1105120-01
E 2013 Nordson Corporation
System Operation
MAC ID / Baud Rate Configuration
Three rotary switches are defined for user configuration of the device. The
three rotary switches are defined as follows:
Rotary switches S2 (MSD) and S3 (LSD) are used to select the DeviceNet
MAC ID address. The valid range of addresses is 0 – 63. All combinations
above 63 set the device address to the last address the device was
powered up at and allow software configuration tools to modify the MAC ID
address.
ADDRESS
MSD LSD
P
0
2
4
6
2
4
6
8
0
Figure 10-1 MAC ID Switches S2 and S3
Rotary switches S1 (BAUD) is used to select the DeviceNet Baud Rate. The
valid range of baud rates is 0−3 (0=125K, 1=250K, 2=500K). All values
above 2 set the baud rate to the last baud rate the device was powered up
at and allow software configuration tools to modify the baud rate.
DATA RATE
500 Kb
250 Kb
125 Kb
PGM
Figure 10-2 Baud Rate Switch S1