User`s manual
—
31
—
Tabl e 17 — 580D150 Air Delivery, Horizontal Discharge Units
NOTES:
1.
Boldface
indicates a field-supplied drive is required. (See Note 8.)
2. indicates an alternate motor and drive are required.
3. indicates a field-supplied motor and drive are required.
4. indicates maximum usable watts of a factory-supplied motor.
5. Maximum usable watts input is 3775 with a standard motor and 4400 with an
alternate motor. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. For additional
information on motor performance, refer to Table 9.
6. Values include losses for filters, unit casing, and wet coils.
7. Use of a field-supplied motor may affect wire sizing. Contact your representa-
tive to verify.
8. Standard motor drive range: 860 to 1080 rpm. Alternate motor drive range:
900 to 1260 rpm. All other rpms require field-supplied drive.
9. To convert watts to bhp:
Motor efficiency = .80 (Std)
.87 (Alt)
B. Ventilation Sequence
If unit is equipped with an Durablade economizer or two-
position damper, the damper will open to the minimum posi-
tion whenever the evaporator fan runs.
The damper motor will be energized with 24-vdc power and
damper will drive open until SW3 on the damper is deacti-
vated. The damper motor will stop and damper will remain
in the minimum ventilation position until the evaporator fan
is shut off. When the evaporator fan is shut off, the damper
motor is again energized and the damper runs closed until
SW2 is activated and the damper motor turns off.
CARE AND MAINTENANCE
To ensure continuing high performance and to minimize the
possibility of premature equipment failure, periodic mainte-
nance must be performed on this equipment. This combina-
tion heating/cooling unit should be inspected at least once
each year by a qualified service person.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
The minimum maintenance requirements for this equipment
are as follows:
1. Inspect air filters each month. Clean or replace when
necessary.
2. Inspect cooling coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness.
Inspect belts, and belt tension each heating and cool-
ing season. Clean, adjust or replace when necessary.
4. Check electrical connections for tightness and con-
trols for proper operation each heating and cooling
season. Service when necessary.
5. Check and inspect heating section before each heat-
ing season. Clean and adjust when necessary.
6. Check and clean vent screen if needed.
AIRFLOW
(Cfm)
STANDARD AND ALTERNATE BELT DRIVE MOTORS
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
3700 677 1129 748 1316 810 1498
869 1700 928 1940 984 2166 1036 2387 1080 2548
1114 2737 1135 2828
3800 691 1194 761 1390 822 1582
880 1776 937 2035 993 2272 1046 2503
1092 2719 1129 2901 1156 3028
3900 705 1267 773 1473 834 1674
891 1862 947 2131 1002 2370 1055 2620
1102 2855 1143 3056 1174 3212
4000 720 1349 786 1548 847 1768
902 1957 957 2228 1011 2485 1064 2737
1112 2983 1155 3212 1190 3405
4100 734 1423 800 1641
860 1871 914 2061 967 2316 1021 2593 1072 2855
1121 3120 1165 3368 1203 3581
4200 749 1506 813 1725
873 1974 926 2175 978 2414 1030 2710
1081 2983 1130 3258 1175 3516 1215 3757
4300 764 1598 826 1828
886 2079 938 2290 989 2521 1040 2837
1090 3111 1139 3396 1185 3664 1226 3925
4400 779 1691 840 1931
899 2193 951 2414 1000 2638 1050 2955
1100 3248 1148 3535 1194 3822 1236 4093
4500 793 1785 854 2035
912 2307 963 2548 1012 2755 1061 3065
1109 3387 1157 3674 1203 3981 1246 4260
4600 808 1888
868 2158 925 2459 975 2674 1024 2901 1071 3184
1119 3525 1166 3832 1212 4130 1255 4437
4700 822 2000
882 2281 937 2548 988 2819 1036 3056
1082 3313 1129 3674 1175 3990 1221 4298 1264 4605
4800 837 2114
896 2414 950 2674 1001 2964 1048 3212
1093 3461 1139 3813 1185 4148 1230 4456 1273 4782
4900 852 2237
910 2548 963 2810 1014 3111 1060 3368
1105 3609 1150 3943 1194 4307 1239 4633 1282 4958
5000
867 2361 924 2683 977 2946 1027 3267 1073 3535
1117 3776 1161 4093 1204 4475 1248 4810 1291 5133
5100
882 2485 938 2828 990 3092 1040 3424
1085 3702 1129 3962 1172 4251 1214 4642 1257 4995 ——
5200
896 2629 952 2973 1003 3248 1053 3590
1098 3869 1141 4148 1183 4419 1225 4791 1267 5170 ——
5300
911 2773 967 3129 1017 3405 1066 3757
1111 4055 1153 4335 1194 4596 1236 4958 ————
5400
926 2919 981 3294 1030 3572
1079 3916 1124 4270 1166 4531 1206 4791 1247 5124 ————
5500
940 3074 995 3461 1044 3748
1092 4093 1137 4437 1178 4726 1218 4958 ——————
5600
955 3239 1010 3627
1058 3943 1105 4270 1150 4633 1190 4930 1230 5124 ——————
5700
970 3405
1024 3804 1072 4139 1118 4456 1163 4837 1203 5143 ————————
5800
985 3581
1039 3981 1086 4335 1131 4652 1176 5041 ——————————
5900
1000 3757
1053 4167 1100 4540 1144 4856 ————————————
6000
1015 3953 1068 4363 1114 4754 1158 5060 ————————————
6100
1030 4139 1083 4558 1128 4967 ——————————————
6200
1046 4344 1097 4763 1142 5180 ——————————————
bhp =
watts input x motor efficiency
746
WARNING: The ability to perform maintenance on
this equipment properly requires certain expertise,
mechanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any mainte-
nance on this equipment other than those procedures
recommended in the User’s Manual. FAILURE TO
HEED THIS WARNING COULD RESULT IN SERI-
OUS PERSONAL INJURY AND POSSIBLE DAM-
AGE TO THIS EQUIPMENT.
WARNING: Failure to follow these warnings could
result in serious personal injury:
1. Turn off gas supply, then turn off electrical
power to the unit before performing any main-
tenance or service on the unit.
2. Use extreme caution when removing panels and
parts. As with any mechanical equipment, per-
sonal injury can result from sharp edges, etc.
3. Never place anything combustible either on, or
in contact with, the unit.
4. Should overheating occur, or the gas supply fail to
shut off, shut off the external main manual gas
valve to the unit, then shut off the electrical supply.