Instruction manual
4 Measurement
38
Control width setting
Set the control widths. The procedures are different depending on the selected control width
type.
When the control width type is “d.diF”
Sets the same width is set both over and under the control value at the center.
1. Open the basic setup menu and press the UP/DOWN keys to display the control
target setting for R1 on the panel, referring to “ How to open basic setup menus”
(page 19).
The setup item selection screen is displayed on the measurement display, showing the
display for control target setting, “1.SEL”.
2. Press the UP/DOWN key to display “1.diF”, and then press the ENT key.
The sub-display starts blinking. Now you can change the setting.
3. Press the UP/DOWN key to select the control width.
UP key : Increments the value by the minimum display unit.
DOWN key : Decrements the value by the minimum display unit.
The setting range is 0.00% to 20% of the measurement range.
4. Press the ENTER key to establish the setting.
Tip
z To set another item of relay output 1 setting next, press the UP/DOWN key to display it.
z To select another setting item, press the MEAS key.
When the control width type is “S.diF”
Different widths are set over and under the control value.
1. Open the basic setup menu and press the UP/DOWN keys to display the control
target setting for R1 on the panel, referring to “ How to open basic setup menus”
(page 19).
The setup item selection screen is displayed on the measurement display, showing the
display for control target setting, “1.SEL”.
2. Press the UP/DOWN key to display “1.udF”, and then press the ENT key.
The sub-display starts blinking. Now you can change the setting.
3. Press the UP/DOWN key to set the control width for under the control value.
UP key : Increments the value by the minimum display unit.
DOWN key : Decrements the value by the minimum display unit.
The setting range is 0.00% to 10% of the measurement range.
4. Press the ENTER key to establish the setting.
The display returns to the contact output setting menu.
5. Press the DOWN key to display “1.odF”, and then press the ENT key.
The sub-display starts blinking. Now you can change the setting.
6. Press the UP/DOWN key to select the control width over the control value.
UP key : Increments the value by the minimum display unit.
DOWN key : Decrements the value by the minimum display unit.
The setting range is 0.00% to 10% of the measurement range.
7. Press the ENTER key to establish the setting.
Tip
z To set another item of relay output 1 setting next, press the UP/DOWN key to display it.
z To select another setting item, press the MEAS key.