1-11 Installation Instructions
Electrical Characteristics
Indoor Unit: ACR 425 H Outdoor Unit : AER 425 SCLE
AER 425 SHLE
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Heating:
Rating Conditions : Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions : Indoor Air Temperature 24°C DB
Outdoor Air Temperature 21°C DB / 15.5°C WB
● Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz
Rating conditions
A 0.43 / 0.43 0.62 / 0.65 12.1 / 12.3 13.15 / 13.38
kW 90 / 100 0.13 / 0.15 2.55 / 2.7 2.77 / 2.95
Full load conditions
A 0.43 / 0.43 0.62 / 0.65 13.44 / 13.48 14.49 / 14.56
kW 90 / 100 0.13 / 0.15 2.8 / 2.88 3.02 / 3.13
Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75
● Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz
Rating conditions
A 0.33 / 0.34 0.62 / 0.65 13.7 / 13.5 14.65 / 14.49
kW 70 / 80 0.13 / 0.15 2.86 / 2.96 3.06 / 3.19
Full load conditions
A 0.33 / 0.34 0.62 / 0.65 15.6 / 15.2 16.55 / 16.19
kW 70 / 80 0.13 / 0.15 3.25 / 3.29 3.45 / 3.52