Technical data
1. Specifications
1
2
3
4
5
I-55
1-3 Other Component Specifications
Concealed Duct Type
MODEL NO. Indoor Unit ADR 425 ~ 448 H
Power Transformer ATR-II215TB
Rated
Primary VAC, Hz 230 V, 50 Hz
Secondary 10.2 V 1.4 A
14 V 0.5 A
Coil resistance Ω WHT –WHT : 110 , BRN – BRN : 0.5
RED – RED : 2.3
Thermal cut off temperature ˚ C 145
Thermistor (Coil sensor) : TH2, 3, 4 PBC-41E-S36 , PBC-41E-S25
Resistance KΩ -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %
-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %
0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %
5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %
10 ˚C : 9.7 ± 5 %
Thermistor (Room sensor) : TH1, 5 KTEC-35-S6, KTEC-35-S85
Resistance KΩ 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %
5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %
10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %
20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %
30 ˚C : 4.0 ± 5 %
Electronic expansion valve
Valve body IKV-24D12 (ADR 425 H)
HKV-30D16 (ADR 436 H - ADR 448 H)
Coil DKV-MOZS697E0 (ADR 425 H)
EKV-MOZS698E0 (ADR 436 H - ADR 448 H)
Drain pump PTV-1422
Rated AC 230 V, 12 W
Float switch FS-0218-103
Rated (Contact rated) DC 12 V, 25 W