Technical data
2. Processes and functions
1
12
3
4
5
II - 18
(1) When the unit is stopped, the Auto-flap returns to F5 position.
(2) When the airflow direction is set (an optional setting), the auto and Swing settings will
be released. To return the mode to auto-flap control, change the operation mode.
(3) Once Auto-flap is set, the flap position will be input in the memory.
(4) When the operation mode is changed, the unit starts to search flap position. (if a
search action for sensing flap position is not succeeded in one minute, only the swing
is operated.)
2-17
Auto-flap Control
(Indoor Unit : 4-Way Air Discharge Semi-Concealed Type
Ceiling-Mounted Type)
Auto flap can control the air flow in 5 steps.
Fig. 21
Operation mode
Flap position
Automatic setting Optional setting
Cooling/dehumidifying F2 F1 • F2 • F3 • Swing
Fan F2 F1 • F2 • F3 • F4 • F5 • Swing
Heating F4 F1 • F2 • F3 • F4 • F5 • Swing
Standby for heating
F2 (The flap returns to the original position after
release of the standby mode.)
1328_M_I
F1
F5
60°
Heating F1~F5
Cooling F1~F3
F2
F3
F4