Technical data
1. Specifications
1
2
3
4
5
I - 117
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : ADR 436 H Outdoor Unit : AER 436 SCL3E
AER 436 SHL3E
● Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 1.43 / 1.54 1.24 / 1.31 6.35 / 6.39 7.13 / 7.19
kW 290 / 340 0.26 / 0.29 3.46 / 3.51 4.01 / 4.14
Full load conditions
A 1.43 / 1.54 1.24 / 1.31 7.2 / 7.24 7.99 / 8.05
kW 290 / 340 0.26 / 0.29 3.98 / 4.02 4.53 / 4.65
Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50
● Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 1.43 / 1.54 1.24 / 1.31 7 / 7.04 7.79 / 7.84
kW 290 / 340 0.26 / 0.29 3.86 / 3.88 4.41 / 4.51
Full load conditions
A 1.43 / 1.54 1.24 / 1.31 7.4 / 7.44 8.19 / 8.25
kW 290 / 340 0.26 / 0.29 4.08 / 7.12 4.63 / 4.75
Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Heating:
Rating Conditions : Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions : Indoor Air Temperature 24°C DB
Outdoor Air Temperature 21°C DB / 15.5°C WB