Technical data
1. Specifications
1
12
3
4
5
I - 114
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : ACR 448 H Outdoor Unit : AER 448 SCL3E
AER 448 SHL3E
● Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 0.95 / 0.98 1.24 / 1.31 7.7 / 7.72 8.35 / 8.38
kW 200 / 220 0.26 / 0.29 4.14 / 4.16 4.6 / 4.67
Full load conditions
A 0.95 / 0.98 1.24 / 1.31 8.8 / 8.82 9.47 / 9.5
kW 200 / 220 0.26 / 0.29 5 / 5.04 5.46 / 5.55
Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58
● Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 0.86 / 0.9 1.24 / 1.31 8.89 / 8.91 9.54 / 9.56
kW 180 / 200 0.26 / 0.29 5.06 / 5.08 5.5 / 5.57
Full load conditions
A 0.86 / 0.9 1.24 / 1.31 9.4 / 9.41 10.05 / 10.07
kW 180 / 200 0.26 / 0.29 5.38 / 5.42 5.82 / 5.91
Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Heating:
Rating Conditions : Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions : Indoor Air Temperature 24°C DB
Outdoor Air Temperature 21°C DB / 15.5°C WB