6.8 Service and Programming Aids
6.8.1 CAN-Assist, Art. no. 502 800-880
PC based tool that in Passive Mode allows listening to the CAN-bus traffic in the
Weld system during the current process.
In Master Mode, with the connection to the robot master disconnected, the I/O-
function in the different units in the system can be activated, parameters loaded or
changed.
CAN-Assist is supplied as a package with hardware and a CD containing software
and documentation.
6.8.2 Indication unit for PIB, Art. no. 505 100-001
Tool that is connected to the 32 way Euro connector on the PIB.
The unit uses light emitting diodes to show the CAN-bus status of the inputs and
outputs on the PIB. The analogue display shows the value of an analogue channel,
the wire feed speed or reference for the weld voltage. Channel selection is made
using 3 push buttons.
6.8.3 Smartac with indication unit, Art. no. 505 100-002
Same as above, but with combined Smartac function.
6.9 Diagnostics – Error Handling
The PIB is fitted with two light-emitting diodes according to the DeviceNet speci-
fication, see Figure 19 on page 35.
One of the diodes has the designation NS (Network Status) and indicates the func-
tion of the CAN bus. The other one has the designation MS (Module Status) and
indicates the PIB function.
Correct function is indicated by a green light coming on and incorrect function by a
red light. During the initiation phase, which can take a few seconds, the light of the
diodes changes.
Exception: On ARCITEC LRA/S4C (jumper TB9 made) does not indicate NS
while MS indicates the status as set out above.
During software execution on the robot (start, stop and current execution) the con-
tinuous transfer from PIB of the function status from the PIB as well as from the
weld process takes place via the sensors connected to the PIB.
In the event of an error on PIB an error message is given to the robot programming
unit as a warning to call action, see the table below. The weld process is not inter-
rupted.
If the error concerns process supervision (shield gas, weld current) the weld proc-
ess is interrupted with the error message "Arc Supervision".
Error messages are acknowledged by pressing OK.