1. SHARP PLC 5-5
Connection to PLCs
Wiring
Indicate the connection of ZM-300 and each module. CN1 is used alternately with RS-422.
RS-232C
• Connection with JW-70CUH/100CUH, JW-70CU/100CU, JW-22CU
• Connection with Z-311J/312J
• Connection with JW-32CUH/H1, JW-33CUH/H1/H2/H3
*
Used shielded cables
Signal name
FG
SD
RD
RS
CS
SG
Pin No.
1
2
3
4
5
7
Signal name
FG
RXD
TXD
SG
Pin No.
1
3
2
7
12
14
(Communication Por
t)
JW-22CU
JW-70CU/100CU
JW-70CUH/100CUH
Short Terminal
ZM-300 (CN1)
*
Used shielded cables
Signal name
FG
SD
RD
RS
CS
SG
Pin No.
1
2
3
4
5
7
Signal name
FG
RDC
TDC
GND
Pin No.
1
3
2
7
6
8
Z-311J/312J
(Host communication port CN
3)
Short Terminal
ZM-300 (CN1)
*
Use twist shielded cables
Signal name
FG
SD
RD
RS
CS
SG
Pin No.
1
2
3
4
5
7
Signal name
FG
RD
SD
SG
Pin No.
1
4
2
7
(PG/COMM2 port)
JW-32CUH/H1
JW-33CUH/H1/H2/H
3
ZM-300 (CN1)