Instruction manual
5
1. SHARP PLC 5-3
Connection to PLCs
(2) System memory setting of JW-32CUH/H1/M1, JW-33CUH/H1/H2/H3, Z-511J/512J
• Communication port 1 (PG/COMM 1 port)
• Communication port 2 (PG/COMM 2 port)
(3) System memory setting of JW-1324K/1342K, JW-1424K/1442K and JW-1624K/1642K
• Communication port
• MMI port
System memory Setting Contents
#234 30 (H)
Stop bit : 2 bit,
Parity : Even
Baud rate:19200 bps
#235 01 (H) Station address
System memory Setting Contents
#236 30 (H)
Stop bit : 2 bit,
Parity : Even
Baud rate:19200 bps
#237 01 (H) Station address
System memory Setting Contents
#234 00 (H) Computer link
#236 30 (H)
Stop bit : 2 bit,
Parity : Even
Baud rate:19200 bps
Data Length : 7 bit
#237 01 (H) Station address
System memory Setting Contents
#226 30 (H)
Stop bit : 2 bit,
Parity : Even
Baud rate:19200 bps
Data Length : 7 bit
#227 01 (H) Station address