Instruction manual

5-2 1. SHARP PLC
JW Series: Link Unit Switch Setting
(1) Switch setting of JW-10CM, ZW-10CM and JW-21CM
(2) Switch setting of Z-331J/332J
JW100/70H COM Port, JW20 COM Port:
System Memory Setting
The settings for communications with the ZM-300 series should be made at the system memory as
shown below.
(1) System memory setting of JW-70CUH/100CUH, JW-70CU/100CU, JW-22CU, and Z-311J/312J
Switch Setting Contents
SW0 4 Comand mode
SW1 1 Station address (lower half)
SW2 0 Station address (upper half)
SW3-1 OFF Not used
SW3-2 ON 4-wire system
SW3-3 OFF Not used
SW3-4 ON Even parity
SW4 0 Baud rate:19200 bps
SW7 ON Termination resistance provided
Switch Setting Contents
SW0 4 Computer link
SW1 1 Station address (lower half)
SW2 0 Station address (upper half)
SW3-1 OFF Not used
SW3-2 OFF Used only for 2-line system
SW3-3 OFF Not used
SW3-4 ON Even parity
SW4 0 Baud rate:19200 bps
SW7 ON Termination resistance provided
System memory Setting Contents
#236 30 (H)
Stop bit : 2 bit,
Parity : Even
Baud rate:19200 bps
#237 01 (H) Station address