Technical data
/08.2011/air/8
D
890/980*
E
C
G
F
A
K
25
20
B
J
EN
Adapter plate with damper or flexible connection
- Connection under the unit
The adapter plate serves to attach a damper or a flexible connection under the unit. First install the actuator onto
the louver shaft on the right side (at the front for Cyberir 3 CW, construction size 1 and 2) looking at the unit front.
Then fix the louver with the actuator under the adapter plate. Now mount the adapter plate with pre-mounted louver
on the floor stand frame by means of bolts. Please take care that the adapter plate does not pass over the frame to
avoid canting of the floor stand within the raised floor.
The damper actuator, which is controlled via a 24 V signal by the controller, has to be electrically connected. For this
the cable, which is already connected at the motor, must be routed through an opening in the adapter plate into the
unit and then be connected at the controller in the electric box according to the electric diagram.
Cabinet size
Knock-out openings for
supply connections
Bottom view
Unit front
Damper height for all units: 120 mm
Flexible connection height for all units: 150 mm
If the air side has to be continued by a duct, the installation of a flexible connection is necessary.
Take into account the installation of pressure compensations in the flexible connection.
C / G
H
38
E/K