Technical data

EN04.2011/humidifier/6
1 Drain/Info key
press key shortly: opens and closes the drain valve (manual draining).
Note: the drain valve is automatically closed after 10 minutes.
press key for a extended period of time: activating the info mode
2 Error indication (red LED)
in normal operating mode
The LED lights in case of a malfunction of the unit. Further operation is no longer possible, the heating
voltage is interrupted. An alarm signal is sent to the C7000 controller. At the C7000AT the alarm "HUMIDI
-
FIER 1 FAILURE" is displayed.
– in info mode
LED blinks in intervals if a malfunction is present. The number of “blinks” per interval indicates the number
of the error (see chapter 12.1.4.3).
3 Warning and info indication (yellow LED)
in normal operating mode
The LED blinks, if manual draining is in progress.
The LED lights if the cylinder maintenance is due or the maintenance indication is not reset after the main
-
tenance.
– in info mode
LED blinks in intervals if a malfunction with status warning is present. The number of “blinks” per interval
indicates the number of the error (see chapter 12.1.4.3).
4 Steam production (green LED)
– in normal operating mode
The LED lights if the unit produces steam.
– in info mode
LED blinks in intervals. The number of “blinks” per interval multiplied by 10 indicates the current steam
output in % (see chapter 12.1.3.3).
12.1.3 Operation
12.1.3.1 Function of the display and operating elements on the control unit ECCM/S