Instruction manual
61 
6. Special Applications 
6.1 Outdoor Application 
If you intend using electronic control gear for T5/∅ 16 mm-  fluorescent 
lamps in outdoor luminaires, it is important to remember that depending on 
the design of the luminaire, it may be exposed to moisture and humidity. 
The level of protection of the luminaire (IP ... according to DIN 40050/IEC 
529) determines whether standard or special ECG have to be installed. 
1)  In luminaires of ingress protection type „5“ (protected against water 
jets: IP 65 for example) standard ECG can be used since dampness 
cannot penetrate this type of luminaire. So there is no risk of the 
ECG being corroded. 
2)  In the case of luminaires of protection type „3“ (protected against 
splash water, IP 43 for example), it is possible that water droplets 
will penetrate and cause corrosion. We therefore recommend using 
a protective housing (OUTKIT) over the ECGs for these luminaires. 
When using QUICKTRONIC
®
 of 21 mm height in combination with  
OUTKIT (see Section 
6.1.2) special attention should be paid to the 
proper strain relief of the ECG in the OUTKIT cases. 
Typical applications include lighting systems for car washes, petrol stations, 
outdoor advertising, swimming poops etc. 
For these applications we recommend to use the ECG in combination with 
OUTKIT. 
6.1.1 Installation 
Instructions 
In addition to general installation and wiring instructions (Section 3) the 
following information is important: 
•  The mains connection terminals on the ECGs should point 
downwards. In other words, the control gear should be installed 
vertically or upside down with the base of the ECG uppermost, 
otherwise horizontally with a slight incline (5 to 10°). This will 
prevent condensate from collecting inside the unit and causing 
short-circuits on the printed circuit board and tripping the RCD as a 
result of leakage currents. 
•  All ECG terminals that are not protected by vertical or upside down 
installation should be covered by arched metal plates or plastics 
(better with regards to corrosion) so that spray water and 
condensate cannot drip into the terminals and therefore into the 
ECG. 
•  Place ECGs on spacers to protect them from dripping 
water/condensation. 
•  To prevent water entering the control gear through the terminals 
along the incoming or outgoing cables, it is best to bend the cables 
ahead of the terminals (to provide a water pocket or drip point). To 
ensure success, the lowest point of the kink should lie below the 
level of the terminal inlet. 
•  A small opening at the lowest point on the luminaire is also 
recommended so that condensation can escape. However, this 
opening should be protected so that rain and spray cannot enter. 










