Instruction manual
51 
3.15  RCDs / Fault Currents 
In the case of ECGs with protective earth (PE) connections, both the high 
short duration starting current and the small continuous current through the 
interference suppression capacitors in the ECG can trip the residual current 
detector (RCD). 
The following solutions may be considered: 
•  Devide the luminaires into three phases and use three-phase RCDs 
•  Use surge-current-resistant, short-delay 
•  Use 30 mA RCDs (if possible) 
In Section 
7.3 are the values for QUICKTRONIC
®
 ECG for operation of 
T5/∅ 16 mm- fluorescent lamps FH
®
...HE and FQ
®
...HO. 
3.16 Leakage Current 
In protection class I luminaires, the internal HF filter in an ECG with PE 
conductor connection produces a 50 Hz leakage current through the earth 
conductor whose value depends on the product type. 
This 50 Hz leakage current limits the number of ECGs that can be operated 
on an RCD. 
For all QUICKTRONIC
®
 units to operate T5/∅ 16 mm-  fluorescent  lamps 
FH
®
...HE and FQ
®
...HO the following applies: 
Leakage current < 0.5 mA 
3.17  ECGs in Three-Phase 
Operation 
When using electronic control gear in a three-phase operation the following 
points have to be considered: 
1.  Check whether the mains voltage is within the application range of 
the ECG (DC/AC range from 198 V to 254 V). 
2.  The mains connection on the installation side may only be made to 
the luminaire terminal. For luminaries or luminaire groups in 3-
phase circuits. 
3. Make absolutely sure that the neutral conductor is correctly 
connected to all the ECG-luminaires and that it is making proper 
contact. 
4.  Cables may only be disconnected or connected when no voltage is 
present. 
5.  For 3x230/240 V supply networks in triangular circuit arrangements, 
protection by way of common disconnection of the phase conductor 
is necessary. 
Important: 
•  In new installations the load must not be connected when the 
insulation resistance is measured with 500 V DC, since according to 
VDE 0100 T600 Section 9 the test voltage is also applied between 
the neutral conductor (N) and all three external lines (L1, L2, L3. In 
existing installations it is sufficient to carry out an insulation test 
between the external lines (L1, L2, L3) and the protective earth 
without disconnecting the loads. The neutral conductor (N) and the 
protective earth (PE) may not be electrically connected in any way 
when this is done. For this insulation measurement (500 V DC to 
earth) the neutral conductor disconnection terminal may only be 
opened with the mains voltage switched off! 










