Instruction manual

48 
3.11 ECG Operation for 
Luminaires of 
Protection Classes I 
and II 
In accordance with EN 60598, luminaires are grouped into protection 
classes according to the measures taken against contact with high 
voltages. 
In the case of protection class I luminaires, all accessible parts which may 
become live as a result of a fault must have a good conductive connection 
to the PE conductor. The conductive link between the luminaire and the 
ECG must not be provided by the PE conductor of the ECG but by 
appropriate mechanical design features (such as using serrated edge 
washers or serrated head bolts). 
In the case of protection class II luminaires, live parts must be provided 
with reinforced or double insulation. Protection class II luminaires do not 
therefore have an earth connection (except protection class II luminaries 
with functional earth). 
ECGs only approved for installation in luminaires are not assigned to a 
protection class since protection classes are defined only for end products 
(such as luminaires) and not for components. 
All QUICKTRONIC
®
 units to operate T5/∅ 16 mm-fluorescent  lamps 
FH
®
...HE and FQ
®
...FO are, in principle, suitable for operation in protection 
class I and II, unless otherwise indicated in the latest edition of the Lighting 
Programme or under www.osram.com/ecg
However, radio interference suppression and temperatures must be 
checked in each case. 
As a general rule, we can say that the thermal properties in open metallic 
luminaires (typically protection class I luminaires) are normally better than 
in enclosed plastic luminaires (typically protection class II luminaires) 
because of the good thermal conductivity of metal (heat sink effect) and 
better convection possibilities in the luminaire. 
3.12  Insulation Distances in 
Luminaires 
The use of luminaires is subject of a series of regulations governing 
electrical safety (shock protection) and operational reliability in wet, dusty, 
corrosive, flammable and explosive conditions. European standard 
EN 60598 applies to the electrical safety of luminaires. 
To guarantee the electrical safety of luminaires, special attention must be 
paid to clearances and tracking distances. These terms are defined as 
follows in EN 60598-1-11 for the mains terminal of the luminaire: 
„Tracking distances at the mains terminal shall be measured between the 
active parts in the terminals an any exposed metal part. Clearance shall be 
measured between the incoming mains cable and exposed metal parts (i.e. 
from the bare end from which the insulation has been stripped the furthest 
to the metal part that is exposed). On the side of the terminal to which the 
internal wires are connected, the clearance shall be measured between the 
active parts and the exposed metal parts.” 
For further information please refer to luminaire standard EN 60598. 
3.13 Insulation Test 
Luminaires must be subjected to insulation and high voltage testing 
(according to EN 60598, VDE 0711, PM 395). Proceed as follows: 
•  Input and output terminals of the ECG – except the PE conductor 
terminal – must be connected conductively with one another. 










