„Hot wires“ are marked on the unit with the shorter cable length. For 
reasons of radio interference suppression and reliable starting, the “hot 
wires” must be kept as short as possible. In other words, you should install 
the ECG to one side in the luminaire, making the low-potential cables 
longer so that the length of the high-potential cables can be reduced. This 
type of installation is to be preferred to symmetrical mounting. 
In luminaires equipped with more than one ECG (systems with 3, 4 or more 
lamps), the ECG and its associated lamp(s) should be assigned to one 
another. For reasons of radio interference suppression and reliable starting 
we do not recommend splitting the luminaire into a lamp and ECG part. 
QUICKTRONIC
®
 ECG for 3- and 4-lamp operation of FH
®
…HE fluorecent 
lamps have been optimally designed to comply with just that 
recommendation. 
For reasons given above we also advise against splitting the ECG into 
units located in the luminaire and units located outside the luminaire (e.g. 
on the back of the luminaire) if this means much longer cables between the 
ECG and the lamps. 
3.5 Switching between 
Lamp and ECG 
In some special applications it may be necessary to disconnect or switch 
the cables between the ECG and the lamp(s). 
If changeover units are used (emergency lighting modules with internal 
switching) which supply the lamp directly from an emergency supply and 
interrupt the system circuit between the ECG and the lamp, the following 
must be observed: 
•  Changeover or disconnection of the lamps from the ECG to the 
external unit must be on all terminals. 
•  When switching back from the external supply to ECG operation, 
the lamp(s) must first be connected at all terminals to the ECG 
before the ECG is supplied with power again, otherwise the cutout 
in the ECG will operate. 
•  Many of these emergency lighting units available on the market do 
not comply with the normal operating conditions of the lamp and will 
therefore damage it. In such cases, OSRAM cannot guarantee that 
the lamp will last as long as indicated. 
Wiring recommendations for OSRAM QUICKTRONIC
®
 ECG for multi-lamp 
operation of T5/∅ 16 mm- fluorescent lamps with exemplary emergency 
units are given in Section 6.5.2ff. 
3.6 Master-Slave Circuit 
An additional single-lamp „slave luminaire“ can be supplied from a two-
lamp ECG installed in a single-lamp „master luminaire“. 
This requires a 4-core connecting cable between the two luminaries and, in 
general, different cable lengths between the ECG and the lamp in the 