Instruction manual

36 
b) Louvre instead of a reflector 
  The same applies to louvers as to reflectors. Louvres also have to be 
  good electrical conductors and be connected to luminaire earth. 
3.3 Permissible Cable 
Lengths 
Section  7.1 refers to the maximum recommended cable lengths between 
the ECG and the lamp. The additional information is discussed elsewhere 
in this section. These maximum recommended cable lengths must be 
adhered to in order not to overload the ECG and to ensure that the system 
will start reliably even under adverse conditions (low ambient temperatures, 
high humidity levels, aged lamps). 
In order to comply with the radio interference suppression limits, the 
instruction in Section xx must be followed. If the maximum recommended 
cable lengths for operating an ECG-lamp system are fully exploited, 
additional radio interference suppression measures may be needed such 
as shielding or separate filters. Because there are so many different 
interference factors involved (see Section 3.2), it is not possible to specify a 
maximum cable length for an ECG-lamp system below which radio 
interference suppression limits are guaranteed not to be exceeded. 
3.4 „Hot Wires“ 
„hot wires“ (high potential). By this we mean the lamp cables which are at 
the highest potential with respect to circuit earth or protective earth. The 
other lamp cables are “cold wires” and have a correspondingly lower 
potential with respect to earth. 










