Appendix 2 Instructions for UL and cUL
(Standard to comply with: UL 508C, CSA C22.2 No.14)
General precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes, and check for residual
voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l inspection, mettez l appareil hors tension et attendez plus
de 10 minutes.
Installation
The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the following conditions.
Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the above specifications. (Refer to .)
Wiring protection
For installation in the United States, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance
with the National Electrical Code and any applicable local codes.
For installation in Canada, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the
Canadian Electrical Code and any applicable local codes.
Maximum allowable rating by the US National Electrical Code. Exact size must be chosen for each installation.
Wiring to the power supply and the motor
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL listed copper, stranded wires (rated at 75°C) and round crimping
terminals. Crimp the crimping terminals with the crimping tool recommended by the terminal maker.
Short circuit ratings
! 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 264 V Maximum.
! 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 550 V or 600 V Maximum.
FR-A820-[]
00046
(0.4K)
00077
(0.75K)
00105
(1.5K)
00167
(2.2K)
00250
(3.7K)
00340
(5.5K)
00490
(7.5K)
00630
(11K)
00770
(15K)
Rated fuse voltage(V) 240V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
152030406080150175200
With power factor
improving reactor
152020305070125150200
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
151525406080110150190
FR-A820-[]
00930
(18.5K)
01250
(22K)
01540
(30K)
01870
(37K)
02330
(45K)
03160
(55K)
03800
(75K)
04750
(90K)
Rated fuse voltage(V) 240V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
225300350400500500
With power factor
improving reactor
200250300350400500600700
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
2253003504505007009001000
FR-A840-[]
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
Rated fuse voltage(V) 500V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
61015203040708090110150175
With power factor
improving reactor
61010152535607090100125150
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
151515203040607090100150175
FR-A840-[]
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
04320
(160K)
04810
(185K)
05470
(220K)
06100
(250K)
06830
(280K)
Rated fuse voltage(V) 500V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
200250300
With power factor
improving reactor
1752002503003504005006007008009001000
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
2252504504505006008009001000120012001200