Specifications
58
APPENDIX
Wiring protection
For installation Class T, Class J, or Class CC fuse or UL 489 Molded Case Circuit Breaker (MCCB) according to the local
directives must be provided.
*1
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
For wiring protection of the converter unit (FR-CC2) refer to the FR-CC2 Instruction Manual-
A.1.3 Short circuit ratings
200V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 264V maximum.
400V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 550V or 600V
maximum.
A.1.4 Machinery directive
The frequency inverter itself is not a machine in the spirit of the EU machinery directive. The start up of the frequency
inverter in a machine is prohibited so long until it has been confirmed that the entire machine complies with the provisions
of Directive 98/37/EC (from 29.12.2009 Machinery Directive 2006/42/EC).
FR-A820-
00046
(0.4K)
00077
(0.75K)
00105
(1.5K)
00167
(2.2K)
00250
(3.7K)
00340
(5.5K)
00490
(7.5K)
00630
(11K)
00770
(15K)
00930
(18.5K)
01250
(22K)
01540
(30K)
Rated fuse voltage [V] 240V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
15 20 30 40 60 80 150 175 200 225 300 350
With power factor
improving reactor
15 20 20 30 50 70 125 150 200 200 250 300
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
15 15 25 40 60 80 110 150 190 225 300 350
FR-A820-
01870
(37K)
02330
(45K)
03160
(55K)
03800
(75K)
04750
(90K)
Rated fuse voltage [V] 240V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
400 500 500 — —
With power factor
improving reactor
350 400 500 600 700
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
450 500 700 900 1000
FR-A840-
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
Rated fuse voltage [V] 500V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
6 1015203040708090110150175
With power factor
improving reactor
6 1010152535607090100125150
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
15 15 15 20 30 40 60 70 90 100 150 175
FR-A840-
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
04320
(160K)
04810
(185K)
05470
(220K)
06100
(250K)
06830
(280K)
Rated fuse voltage [V] 500V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
200 250 300 — — ―――――――
With power factor
improving reactor
175 200 250 300 350 400 500 600 700 800 900 1000
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
225 250 450 450 500 600 800 900 1000 1200 1200 1200
FR-A846-
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
Rated fuse voltage [V] 500V or more
Fuse Maximum allowable rating [A]
*1
6 1010152535607090100
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
15 15 15 20 30 40 60 70 90 100